Flexible metallic tubing: Type FMT.
Municipal Code of Chicago § 14E-3-360
in effect14E-3-360 Flexible metallic tubing: Type FMT.
The provisions of Article 360 of NFPA 70 are adopted by reference with the following modifications:
1. Revise subsections 360.10(1) through (4) to read:
"(1) Branch circuits not exceeding 20 amperes and 300 volts to ground
(2) As permitted in 300.22(C)
(3) Connection between a junction box and a single luminaire
(4) Connection between a junction box and speakers or similar equipment requiring flexibility"
2. Insert new subsection 360.12(7) to read:
"(7) Other than as specifically permitted in 360.10"