Section 903.4 Sprinkler System Supervision & Alarms, Amended.
El Paso City Code § 9.52.080.11
in effect9.52.080.11 - Section 903.4 Sprinkler System Supervision & Alarms, Amended.
903.4 Sprinkler System Supervision & Alarms.
Valves controlling the water supply for automatic sprinkler systems, pumps, tanks, water levels and temperatures, critical air pressure, underground gate valves, and water flow switches on all sprinkler systems shall be electrically supervised by a listed fire alarm control unit or as approved by the authority having jurisdiction.
Exceptions:
1. Automatic sprinkler systems protecting one- and two-family dwellings.
2. Limited area sprinkler systems installed in accordance with Section 903.3.8.
3. Automatic sprinkler systems installed in accordance with NFPA 13R where a common supply main is used to supply both domestic water and the automatic sprinkler system and a separate shutoff valve for the automatic sprinkler is not provided.
4. Jockey pump control valves that are sealed or locked in the open position.
5. Control valves to commercial kitchen hoods, paint spray booths or dip tanks that are sealed or locked in the open position.
6. Valves controlling the fuel supply to fire pump engines that are sealed or locked in the open position.
7. Trim valves to pressure switches in dry, preaction and deluge sprinkler systems that are sealed or locked in the open position.
8. Underground key or hub gate valves in roadway boxes
(Ord. No. 019521, § 1, 7-5-2023)