§ 9.52.080.12 — Section 903.4.2 Alarms, amended

El Paso City Code (Supp. No. 95, Update 4: codified through Ordinance No. 019889, enacted June 23, 2026) · El Paso City Code § 9.52.080.12

Corpus is an independent public-information project, not the official City of El Paso website. Stable reference: corpuslaw.us/code/ddf0d5f1-c0c6-41ac-b2f9-47c9444c7730

9.52.080.12 - Section 903.4.2 Alarms, amended.

903.4.2 Alarms. An approved audible device, located on the exterior and interior of the building in an approved location, shall be connected to each automatic sprinkler system. Such sprinkler water flow alarm devices shall be activated by water flow equivalent to the flow of a single sprinkler of the smallest orifice size installed in the system. Where a fire alarm system is installed, actuation of the automatic sprinkler system shall actuate the building fire alarm system.

(Ord. No. 019521, § 1, 7-5-2023)