9.52.080.19 - Section 903.7 Buildings with Multiple Risers, Added

903.7 Buildings with Multiple Risers. When a building is served by multiple sprinkler system risers, all of the risers shall be served by a manifold system. If the risers are not served by a manifold system, the separate systems boundaries must be clear and able to be described by the addressable fire alarm system.

(Ord. No. 019521, § 1, 7-5-2023)