Section 311.4 Required separation for Group S tenants, added.
El Paso City Code § 18.08.060
in effect18.08.060 - Section 311.4 Required separation for Group S tenants, added.
International Building Code, 2021 Edition, Section 311.4 Required separation for Group S tenants, is hereby added to read as follows:
311.4 Required Separation for Group S Tenants. Tenants of a Group S occupancy shall be separated from other tenants by 1-hour fire partitions and horizontal assemblies or a Code required fire barrier. Non-fire rated partitions may be used to separate Group S tenants provided no area between partitions rated at 1-hour or more exceeds 3,000 sq. ft. or a sprinkler system is installed