Section 1001.7. Postconstruction Building Flush-out and Air Monitoring {As in IgCC}
1001.7.1 Postconstruction, preoccupancy flush-out. {As in IgCC}
1001.7.2 Postconstruction, preoccupancy baseline IAQ monitoring.
Baseline IAQ testing shall be conducted after construction ends and prior to occupancy. Testing shall be performed using protocols consistent with the USEPA Compendium of Methods for the Determination of Toxic Organic Pollutants in Ambient Air, TO- 1, TO-11, TO-17, and ASTM Standard Method D 5197. The testing must demonstrate that the contaminant maximum concentrations listed in Table 1001.7.2 3.1.5 are not exceeded in the return airstreams of the HVAC systems that serve the space intended for occupancy. If the return airstream of the HVAC system serving the space intended for occupancy cannot be separated from other spaces, then for each portion of the building served by a separate ventilation system, the testing must demonstrate that the contaminant maximum concentrations at breathing zone listed in Table 1001.7.2 3.1.5 are not exceeded in the larger of the following number of locations: (i) no fewer than one location per 25,000 ft2 (2500 m2) or (ii) in each contiguous floor area. For each sampling point where the maximum concentration limits are exceeded, conduct additional flush-out with outdoor air, and retest the specific parameters exceeded to demonstrate that the requirements are achieved. Repeat procedure twice. When retesting noncomplying building areas, take samples from the same locations as in the first test.
Table 1001.7.2 Maximum Concentration of Air Pollutants relevant to IAQ
Contaminant | Minimum Concentration, μg/m3 (Unless Otherwise Noted)
Nonvolatile Organic Compounds
Carbon monoxide (CO) | 9 ppm and no greater than 2 ppm above outdoor levels
Ozone | 0.075 ppm (2 h)
Particulates (PM 2.5) | 35 (2 h)
Particulates (PM 10) | 150 (2 h)
Volatile Organic Compounds
Acetaldehyde | 140
Acrylonitrile | 5
Benzene | 60
1,3-butadiene | 20
t-butyl methyl ether (methyl-t-butyl ether) | 8000
Carbon disulfide | 800
Carbon tetrachloride | 40
Chlorobenzene | 1000
Chloroform | 300
1,4-dichlorobenzene | 800
Dichloromethane | 400
1,4-Dioxane | 3000
Ethylbenzene | 2000
Ethylene glycol | 400
Formaldehyde | 33
n-Hexane | 7000
Naphthalene | 9
Phenol | 200
4-phenylcyclohexene (4 PCH) a | 2.5
2-propanol (isopropanol) | 7000
Styrene | 900
Tetrachloroethene (tetrachloroethylene, perchloroethylene) | 35
Toluene | 300
1,1,1-trichloroethane (methyl chlorofoam) | 1000
Trichloroethene (trichloroethylene) | 600
Xylene isomers | 700
Total volatile organic compounds (TVOC) | _____ b
a. This test is only required if carpets and fabrics with styrene butadiene rubber (SBR) latex backing material are installed as part of the base building systems. b. TVOC reporting must be in accordance with CDPH/EHLB/Standard Method V1.1 and must be in conjunction with the individual VOCs listed
(Ord. 24-341 Section 1.)