For AI agents: read the machine-readable documentation index at /llms.txt or the single-file full reference at /llms-full.txt.

§ 49-1560 — Hydrant clear space

Omaha Municipal Code (Supp. No. 100, Update 2: codified through Ordinance No. 44760, enacted August 4, 2026) · Omaha Municipal Code § 49-1560

Corpus is an independent public-information project, not the official City of Omaha website. Stable reference URL

Sec. 49-1560. - Hydrant clear space.

(a) There shall be a minimum of three feet of clear space in each direction around the hydrant base. (b) The hydrant shall be clear of all visual obstructions (bushes, trees and protective barriers, etc.). (c) Protection. (1) Eight-inch schedule 40 steel bollards will be required when located in a parking lot or truck delivery lanes and dock areas. (See Figures 49-1525 and 49-1560.) (2) The hole for the bollard shall be eight inches larger than the outside diameter of the pipe. The pipe shall be centered in the hole and the hole filled with concrete. (i) The concrete shall be 3,000 pound rated. (ii) The pipe shall be filled with concrete.

(Ord. No. 40524, § 1, 10-20-15; Ord. No. 42654, § 50, 8-13-21)