Section 903.4.4 Multi-Tenant and Warehouse Buildings, Added.
El Paso City Code § 9.52.080.14
in effect9.52.080.14 - Section 903.4.4 Multi-Tenant and Warehouse Buildings, Added.
903.4.4.1 Multi-Tenant Buildings, Added.
In buildings requiring sprinkler systems with multiple tenants, where no fire alarm is required, each tenant will have the minimum of one notification device (horn/strobe) to provide audio and visual notification upon activation of the monitoring alarm system, in a location approved by the AHJ.
903.4.4.2 Warehouse buildings (S1/S2) Office Areas, Added.
In warehouse buildings requiring sprinkler systems, where no fire alarm is required, a notification device shall be provided in normally occupied office areas. One device per office area if more than one office area exists and-or one device per level of office area if more than one level exists. Notification devices shall also be provided in storage areas where audio and visual notification would be evident within those areas.
903.4.4.3 Warehouse Buildings (S1/S2) Storage Areas, Added.
In warehouse buildings requiring sprinkler systems and where no fire alarm is required. notification devices shall be provided in storage areas spaced at 3 times the distance required for a full notification system (triple spaced between devices).
(Ord. No. 019521, § 1, 7-5-2023)