Section 903.4.3 amended - Alarms.
Riverside Municipal Code § 16.32.336
in effect16.32.336 - Section 903.4.3 amended - Alarms.
Section 903.4.3 is amended as follows:
An approved audible and visual sprinkler waterflow alarm device, located on the exterior of the building in an approved location, shall be connected to each automatic sprinkler system. Such sprinkler waterflow alarm devices shall be activated by water flow equivalent to the flow of a single sprinkler of the smallest orifice size installed in the system. Where a waterflow switch is required by Section 903.4.1 to be electrically supervised, such sprinkler waterflow alarm devices shall be powered by a fire alarm control unit or, where provided, a fire alarm system. Where a fire alarm system is provided, actuation of the automatic sprinkler system shall actuate the building fire alarm system.
Exception: Removed
(Ord. 7745, § 1(Exh. A), 2025)
Source: City of Riverside, California, Municipal Code and City Charter (Municode Library, library.municode.com)URL: https://library.municode.com/ca/riverside/codes/code_of_ordinances?nodeId=PTIICOOR_TIT16BUCO_CH16.32FIPR_16.32.336SE903.4.3AMLAFetched: 11/1/2026