16.32.340 - Section 907.6.6 added—Monitoring.
Section 907.6 is amended by adding Section 907.6.6 to read as follows: 1. Automatic fire alarm systems shall be monitored and shall transmit the alarm, supervisory and trouble signals to an approved supervising station in accordance with NFPA 72. The supervising station shall be listed as either UUFX (Central Station) by the Underwriters Laboratory Inc. (UL) or other approved listing and testing laboratory or shall comply with the requirements of FM 3011 or ETL. 2. Any existing fire alarm or fire sprinkler monitoring system that has more than six false alarm responses within a year's time frame shall comply with the System Certification Process by UL, FM, or ETL. A false alarm is the willful and knowing initiation or transmission of a signal, message or other notification of an event of fire when no such danger exists.
(Ord. 7745, § 1(Exh. A), 2025)