§ 16.32.336 — Section 903.4.3 amended - Alarms
Riverside Municipal Code (Supp. No. 33: codified through Ordinance No. 7776, enacted June 23, 2026) · Riverside Municipal Code § 16.32.336
Corpus is an independent public-information project, not the official City of Riverside website. Stable reference: corpuslaw.us/code/46dfdebb-19ff-4462-ad22-8d53d3db4cc9
16.32.336 - Section 903.4.3 amended - Alarms.
Section 903.4.3 is amended as follows: An approved audible and visual sprinkler waterflow alarm device, located on the exterior of the building in an approved location, shall be connected to each automatic sprinkler system. Such sprinkler waterflow alarm devices shall be activated by water flow equivalent to the flow of a single sprinkler of the smallest orifice size installed in the system. Where a waterflow switch is required by Section 903.4.1 to be electrically supervised, such sprinkler waterflow alarm devices shall be powered by a fire alarm control unit or, where provided, a fire alarm system. Where a fire alarm system is provided, actuation of the automatic sprinkler system shall actuate the building fire alarm system. Exception: Removed
(Ord. 7745, § 1(Exh. A), 2025)