Austin City Code § 15-13-41 PATHOGENIC MICROORGANISM CONTROL LOG REDUCTION CREDITS AND CONTINUOUS MONITORING.
§ 15-13-41 - PATHOGENIC MICROORGANISM CONTROL LOG REDUCTION CREDITS AND CONTINUOUS MONITORING.
(A) A project applicant shall design and construct an OWRS to meet the requirements in this section.
(B) A permittee shall maintain and operate an OWRS to meet the requirements in this section.
(C) Each treatment process used to meet a log reduction target must include continuous monitoring using the pathogenic microorganisms of concern or a microbial, chemical, or physical surrogate parameter(s) that verifies the performance of each treatment process's ability to achieve its credited log reduction.
(D) An engineering report must include evidence that the treatment unit process can reliably and consistently achieve a specific log reduction value. The engineering report must also include information about the required operating conditions and the type of continuous monitoring to be utilized.
(E) Table 4 identifies the log reduction credits that will be granted for different unit processes and includes examples of required supporting information.
(F) For unit processes that require a validation report, the permittee shall submit a validation report that includes:
(1) evidence of the treatment technology's ability to reliably and consistently achieve the log reduction value;
(2) information about the required operating conditions and surrogate parameters that require continuous monitoring; and
(3) a letter that demonstrates a state public health official previously accepted the report.
Table 4: Treatment Process Log Reduction Credits
Treatment Process | Maximum1Log Reduction Credits Virus/Protozoa/Bacteria | Information to be Included in an Engineering Report | Continuous Monitoring Requirements
Microfiltration or Ultrafiltration | 0/4/0 | Description and calculation of how the system defines an acceptable pressure decay test value per the EPA's Membrane Filtration Guidance Manual to detect 3.0 µm breach | Daily pressure decay test Effluent Turbidity
Membrane Biological Reactor (MBR) | 1.5/2/4 | Operation within the Tier 1 operating envelope 2 | Effluent Turbidity
Reverse Osmosis | 2/2/2 (Dependent on surrogate parameter) | Manufacturer's information indicating ability to reject sodium chloride and description of/rationale for surrogate parameter used to calculate log removal credits | Influent and Effluent Total Organic Carbon (TOC) Or Influent and Effluent Electrical Conductivity
Ultraviolet (UV) Light Disinfection | 6/6/6 (Dose Dependent) | UV reactor's Validation Report following state-approved procedures 3 or NSF/ANSI 55 Class A validated | UV intensity Flow rate
Chlorine Disinfection | 5/0/0 (CT dependent) Bacteria credit equivalent to virus credit can be granted if free chlorine is preceded by membrane filtration and up to 4-log removal for other filtration processes | Calculations demonstrating CT disinfection (CT = Chlorine Residual Concentration × Contact Time) Specifics on how concentration and contact time will be determined | Free chlorine residual Flow rate
Ozone Disinfection | 4/3/4 4 (CT dependent) | Calculations demonstrating CT disinfection (CT = Ozone Residual Concentration × Contact Time) Specifics on how concentration and contact time will be determined | Ozone residual Flow rate
1 Projects may seek higher credit with site-specific validation, alternative surrogates, or other approved methods.
2 Tier 1 operating envelope is defined in the AWRCE Membrane bio-reactor WaterVal validation protocol, Australian Water Recycling Center of Excellence (AWRCE), Brisbane.
3 UV Log Reduction Credits are reactor-specific and dose dependent. UV Validation Reports shall be prepared by a licensed engineer. Validation reports must provide evidence of reactor's ability to reliably and consistently achieve the log reduction value, including information on the required operating conditions and surrogate parameters that require continuous monitoring. The Validation Report shall document results based on validation testing finished utilizing one of the following: EPA UV Disinfection Guidance Manual (USEPA 2006), German UV Devices for the Disinfection for Drinking Water Supply Standard (DVGW 2006), or NWRI UV Disinfection: Guidelines for Drinking Water and Water Reuse, 3rd edition (NWRI 2012). Submitted validation reports must include a letter demonstrating the report has been accepted previously by a state public health official.
4 Bacteria credit can be obtained for ozone according to the Tier 1 framework in the AWRCE Ozone WaterVal Validation protocol, which includes CT tables for waters with turbidity <0.15 NTU.
Source: Ord. No. 20201210-006, Pt. 2, 12-21-20.