§ 14E-3-310 — Conductors for general wiring

Municipal Code of Chicago (2026 S-74, current through Council Journal of June 17, 2026) · Municipal Code of Chicago § 14E-3-310

Corpus is an independent public-information project, not the official City of Chicago website. Stable reference: corpuslaw.us/code/9e560175-9b7b-4444-92bf-3face2672609

14E-3-310 Conductors for general wiring.

The provisions of Article 310 of NFPA 70 are adopted by reference with the following modifications: 1. Insert the following language immediately before informational note no. 1 in subsection 310.15(B)(3)(a): "No more than nine current-carrying conductors shall be permitted to be installed in a raceway other than nipples." 2. Revise table 310.15(B)(3)(a) to read: Number of Current- Carrying Conductors | Percent of Values in Table 310.15(B)(16) through Table 310.15(B)(19) as Adjusted for Ambient Temperature if Necessary 4 – 6 | 80 7 – 9 | 70 (Amend Coun. J. 4-10-19, p. 100029, Art. VI, § 2)