For AI agents: read the machine-readable documentation index at /llms.txt or the single-file full reference at /llms-full.txt.

§ 14E-3-350 — Liquidtight flexible metal conduit: Type LFMC

Municipal Code of Chicago (2026 S-74, current through Council Journal of June 17, 2026) · Municipal Code of Chicago § 14E-3-350

Corpus is an independent public-information project, not the official City of Chicago website. Stable reference: corpuslaw.us/code/c19959e2-0e65-4d68-835c-788a421a34b8

14E-3-350 Liquidtight flexible metal conduit: Type LFMC.

The provisions of Article 350 of NFPA 70 are adopted by reference with the following modifications: 1. Delete subsection 350.10(3). 2. Insert new subsections 350.10(3) through (5) to read: "(3) For the connection of motors and recessed luminaires in a non-plenum ceiling (4) In lengths not exceeding 1.8 m (6 ft) between junction boxes for branch circuits in concealed work fished into existing walls, partitions, floors, or hard surface ceilings where other work does not require or include removal of the existing finished surface (5) For required flexibility at the terminations of conduit runs." 3. Insert new subsections 350.12(3) through (7) to read: "(3) In hoistways, other than as permitted in 620.21(A)(1) (4) In storage battery rooms (5) In any hazardous (classified) location except as permitted by other articles in this Code (6) Where exposed to materials having a deteriorating effect on the installed conductors, such as oil or gasoline (7) Underground or embedded in poured concrete or aggregate"

Ask a question about Chicago law

Corpus searches the Chicago sections it holds and shows the ones that match, with their citations. Free, no sign-in.