§ 14X-5-502.7.4.2.1 — Chute intake direct from corridor

Municipal Code of Chicago (2026 S-74, current through Council Journal of June 17, 2026) · Municipal Code of Chicago § 14X-5-502.7.4.2.1

Corpus is an independent public-information project, not the official City of Chicago website. Stable reference: corpuslaw.us/code/8e8a420f-2914-4dd1-8e76-86af35efa4e0

14X-5-502.7.4.2.1 Chute intake direct from corridor.

Where intake to chutes is direct from a corridor, the intake opening must be equipped with a chute- intake door in accordance with Section 716 of the Chicago Building Code and having a fire protection rating of not less than 1 hour.