14X-5-502.7.4.2.2 Chute intake via a chute-intake room.
Where the intake to chutes is accessed through a chute-intake room, the room must be enclosed with 1-hour fire-resistance-rated construction. Opening protectives for the intake room must be provided in accordance with Section 716 of the Chicago Building Code and have a fire protection rating of not less than 3/4 hour. Opening protectives for the chute enclosure must be in accordance with Section 14X-5-502.7.4.2.1.