§ 5-1A-3 — AMENDMENTS:
Municipal Code of Naperville, Illinois (Supp. No. 101: codified through Ordinance No. 26-049, adopted May 19, 2026) · Naperville Municipal Code § 5-1A-3
Corpus is an independent public-information project, not the official City of Naperville website. Stable reference: corpuslaw.us/code/fd828340-fae3-4997-b5db-d1bd48986ac7
5-1A-3: - AMENDMENTS:
The various sections and tables of the International Building Code 2024 adopted by this Article shall be revised as follows: Section 103.1 Department Of Building Safety: Change to read: The chief building official shall serve as the code official for the city of Naperville. The code official shall serve under the administrative direction of the city manager or a duly authorized designee. Section 103.2 Appointment: Delete in its entirety. Section 103.3 Deputies: Change to read: The code official, with the approval of the city manager or a duly authorized designee, is authorized to designate one or more employees who shall exercise all powers of the code official during any temporary absence or disability of the code official. Section 104.10 Modifications: Add the following: Such modifications shall not have the effect of waiving any provisions of the Naperville municipal code. Section 105.2 Work Exempt From Permit: Delete nos. 1, 3, 6, 8, 9 and change no. 2 to read: Fences not over 3 feet high. Section 105.8 Condition Of Permit: No permit shall be issued to allow the construction, alteration, or remodeling of any building or structure unless: (1) The lot or parcel of real estate upon which the building or structure is located or is to be constructed is fully improved in accordance with title 7 of this code; or (2) The owner of the lot or parcel of real estate upon which the building or structure is located or is to be constructed shall agree, in writing, to fully comply with all of the requirements of title 7 and to construct all of the improvements required by said title, provided, however; (3) That any such lot or parcel of real estate or any construction thereon shall be directly adjacent to and accessible from a hard surface roadway at a location approved by the city engineer and the fire department. (4) Said roadway shall be hard surface of sufficient width, strength, and composition to permit reasonably unimpaired access to such lot or parcel of real estate by emergency, utility service, snow removal, and waste removal vehicles in all weather conditions. (5) Sidewalks: A permittee shall construct public sidewalks within adjacent right-of-way abutting such lot or tract in accordance with provisions of the Naperville municipal code. (6) No permit required by this section shall be issued for the construction of a new principal structure unless: A certified final plat of subdivision, assessment, or planned unit development, as required by the Plat Act (765 ILCS 205/) and title 7 of this code, for the lot or parcel has been recorded in the office of the recorder of deeds in the county in which the lot or parcel is situated. (7) No permit required by this section shall be issued for the construction of a new principal structure unless the applicant shall sign a statement stating that: (a) He or she is familiar with the final engineering plans for the proposed construction site and the final engineering plans are approved pursuant to title 7 of this code; (b) He or she shall comply with the said approved final engineering plans and all requirements of said title 7; (c) Upon completion of the foundation walls and any structural elements which are a necessary part of the construction of the foundation walls, or are necessary for the completion of the foundation walls, and before proceeding with further construction, he or she shall file with the department, a survey, prepared and signed by a registered Illinois land surveyor, showing the location of the structure and the elevation of the top of the foundation walls at all four (4) corners for which a foundation permit has been issued. Section 107.2.1. Information On Construction Documents: Add the following: The maximum size of construction documents shall be limited to 36" x 24" paper unless approved by the building official. One complete electronic version (PDF format) of the final construction "as built" dimensions as approved by the building official shall be submitted to the city of Naperville prior to the issuance of the final occupancy. Deviations from the size requirement may be approved by the code official. Section 108 Temporary Structures And Uses: Delete in its entirety. See sections 5-2D-2, 5-2B-6, and 6-2-11 of the Naperville municipal code. Section 109.4 Work Commencing Before Permit Issuance: Any person who commences any work on a building structure, electrical, gas, mechanical or plumbing system before obtaining the necessary permits shall be subject to penalties as prescribed by law and/or subject to permit fees, including double the cost for inspections and administrative fees as outlined in Title 1, Chapter 9, Article H, Fees for Construction, in the Naperville Municipal Code, or a fee of $500, whichever is greater. Said work shall be subject to a stop work order until such time that the required permits, inspections, and any other necessary approvals, such as zoning variances and/or easement encroachment agreements, have been obtained. If said permits, inspections, or other necessary approvals cannot be obtained, the City may require the applicant to remove the subject improvement. For work that has been completed without a permit and for which required inspections cannot be completed, the City may require the permit applicant to submit verification from a third-party contractor that said work has been completed per Naperville Code requirements. Section 109.6 Refunds: Delete in its entirety. Section 110.4 Inspection Agencies: Add the following language: A written request to use a third-party inspection agency must be submitted to and be approved by the building official prior to the commencement of the inspection. Section 114.4 Violation Penalties: Change to read: Any person who violates a provision of the code or fails to comply with any of the requirements thereof or who erects, constructs, alters or repairs a building or structure in violation of the approved construction documents or directive of the building official, or of a permit or certificate issued under the provisions of this code shall be subject to penalties as prescribed by law and/or subject to permit fees, including double the cost for inspections and administrative fees as outlined in title 1, chapter 9, article H, Fees For Construction, in the Naperville municipal code, and shall be subject to a stop work order until such time a permit for the work is obtained. Section 419.1 General: Change to read: A live/work unit shall comply with Sections 419.1 through 419.9. Exception: A dwelling complying with uses and requirements of Section 6-2-8 "HOME OCCUPATION REGULATIONS" as provided for in Title 6 of the Municipal Code may be classified as a single-family dwelling. Section 703.3 Alternative Methods For Determining Fire Resistance: Delete the following: Delete no. 2 Section 721 Prescriptive Fire Resistance: Delete this section in its entirety. Section 903.2.1.1 Group A-1: Change #1 and add #5 to read: 1. The fire area exceeds 5,000 square feet. 5. Where the combined area of all use group fire areas on all floors, including any mezzanines exceeds 5,000 square feet. Section 903.2.1.2 Group A-2: Change #1 and add #4 to read as follows: 1. The fire area exceeds 2,500 square feet. 4. Where the combined area of all group A-2 fire areas on all floors, including any mezzanines exceeds 2,500 square feet or where the building or structure combined fire area for all use groups located on all floors, including any mezzanines exceeds 2,500 square feet. Section 903.2.1.3 Group A-3: Change #1 and add #4 to read as follows: 1. The fire area exceeds 5,000 square feet. 4. Where the combined area of all use group fire areas on all floors, including any mezzanines exceeds 5,000 square feet. Section 903.2.1.4 Group A-4: Change #1 and add #4 to read: 1. The fire area exceeds 5,000 square feet. 4. Where the combined area of all use group fire areas on all floors, including any mezzanines exceeds 5,000 square feet. Section 903.2.1.13 Group B: Add the following: An automatic sprinkler system shall be provided throughout buildings containing a group B occupancy where one of the following conditions exist: 1. Where a group B fire area exceeds 5,000 square feet. 2. Where a group B fire area is located more than two (2) stories above grade plane. 3. Where the combined area of all use group fire areas on all floors, including any mezzanines exceeds 5,000 square feet. Section 903.2.3 Group E: Delete the exception; also, change #1 and add #4 to read as follows: 1. Throughout all group E fire areas greater than 2,500 square feet in area. 4. Where the combined area of all group E fire areas on all floors, including mezzanines exceeds 2,500 square feet or where the building or structure combined fire area for all use groups located on all floors, including any mezzanines, exceeds 2,500 square feet. Section 903.2.4 Group F: Change #1, 2, and 3 to read as follows: An automatic sprinkler system shall be provided throughout all buildings containing use group F occupancy where one of the following conditions exists: 1. Where a group F fire area exceeds 5,000 square feet. 2. Where a group F fire area is located more than 3 stories above grade plane; or 3. Where the combined area of all use group F fire areas on all floors, including any mezzanines, exceeds 5,000 square feet. Section 903.2.6 Group I: Delete exceptions #1. 2. and 3. Section 903.2.7 Group M: Change #1 and 3 to read as follows: 1. Where a group M fire area exceeds 5,000 square feet. 3. Where the combined area of all use group fire areas on all floors, including any mezzanines, exceeds 5,000 square feet. Section 903.2.8.1: Group R-3: Change to read: An automatic sprinkler system installed in accordance with Section 903.3.1.2 or 903.3.1.1 shall be permitted in Group R3 occupancies. Section 903.2.8.2: Group R-4, Condition 1: An automatic sprinkler system installed in accordance with Section 903.3.1.2 or 903.3.1.1 shall be permitted in Group R-4, Condition 1 occupancies. Section 903.2.8.3: Change to read: Care Facilities: An automatic sprinkler system installed in accordance with Section 903.3.1.2 shall be permitted in care facilities with five or fewer individuals in a single-family dwelling. Section 903.2.8.4 Delete in its entirety. Section 903.2.9 Group S-1: Change #1, 2, and 3 to read as follows: An automatic sprinkler system shall be provided throughout all buildings containing a Group S-1 occupancy where one of the following conditions exists: 1. A group S-1 fire area exceeds 5,000 square feet. 2. A group S-1 fire area is located more than 2 stories above grade plane, or 3. The combined area of all Group S-1 fire areas on all floors, including any mezzanines, exceeds 5,000 square feet. Section 903.2.9.1 Repair Garages: Change #1 and 2 to read as follows: 1. Buildings have two or more stories above grade plan, including basements, with a fire area containing a repair garage exceeding 5,000 square feet. 2. Buildings not more than one story above grade plan, with a fire area containing a repair garage exceeding 5,000 square feet. Section 903.2.10 Group S-2 enclosed parking garages: Change to read: All new parking garages per the National Fire Protection Association (NFPA) 88A shall require automatic fire sprinklers. Section 903.2.11.3 Buildings 55 feet or more in height. Delete the exceptions. Section 903.3.1.1.1 Exempt Locations: Delete the following: Delete #3 through #6. Section 903.3.1.2.3 Attics. Delete subsections 3.2, 3.3 and 3.4. Section 903.3.1.3 NFPA 13D Sprinkler Systems: Change to read: Automatic sprinkler systems installed in one- and two-family dwellings shall be permitted to be installed throughout, including garages, in accordance with NFPA 13D; Group R-3, Group R-4, Condition 1 and townhouses shall be permitted to be installed throughout including garages in accordance with NFPA 13R. Section 903.4 Sprinkler Systems Supervision and Alarm: Delete: Exceptions #3 through #7. Section 905.3 Required Installations. Delete the exception. Section 905.3.1 Height: Add as follows: Class III standpipe systems shall also be installed throughout buildings where the floor level of the highest story is three (3) stories with 25-foot corridors in length and all buildings which are four (4) stories in height, including penthouses. Section 905.3.9: Add the following: All Use Groups: Without exception, a class 1 or class 3 standpipe system shall be installed in all buildings where any portion of the building floor area is more than 400 feet of travel from the nearest point of fire department vehicle access. Section 907.2 Where Required: Change the first paragraph to read as follows: An approved manual, automatic, or manual and automatic fire alarm system installed in accordance with the provisions of this code, NFPA 72, and the current edition of the Naperville fire department's regulations for the installation, maintenance, and testing of fire alarm systems, as amended from time to time, shall be provided in new buildings and structures in accordance with sections 907.2.1 through 907.2.24 and provide occupant notification in accordance with section 907.5, unless other requirements are provided by another section of this code. Where automatic sprinkler protection installed in accordance with section 903.3.1.1 or 903.3.1.2 is provided and connected to the building fire alarm system, automatic heat detection required by this section shall not be required in the area covered by the sprinkler heads. Section 907.2: Add the following subsection: Section 907.2.24: Fire alarm and detection systems for townhouses shall be installed in multiple single-family dwellings (townhouses), if the building or structure contains three (3) or more units. All fire alarm and detection systems shall be listed and installed in accordance with the provisions of NFPA 72, the IBC 2024, the IFC 2024, and the current edition of the Naperville fire department's regulations for the installation, maintenance, and testing of fire alarm systems, as amended from time to time. Table 1607.1 Minimum Uniformly Distributed Live Loads And Minimum Concentrated Live Loads g : Change to read as follows: 5. Balconies and decks: Uniform (psf) = 100, and in no case less than the occupancy served. Section 3001: Delete this section in its entirety and add the following: The design, construction, installation, alteration, repair and maintenance of elevators and conveying systems and their components shall conform to the current state mandated Illinois Elevator Safety Rules, 41 ILL. Adm. Code 1000.60, as amended from time to time. Section 3306.5 Barriers: Change to read as follows: Barriers shall consist of a chain link fence, six feet in height, and shall be placed on the side of the walkway nearest the construction. Barriers shall extend the entire length of the construction site. Openings in such barriers shall be protected by doors or gates which are normally kept closed. Section 3307.2 Protection of Adjoining Property: Add the following language: When the construction or demolition takes place on a lot adjoining residentially zoned properties the site safety regulations in section 5-2B-8 of the municipal code shall apply. Section 3401.3 Compliance: Add the following: Section 3401.3.1: A change of use, addition, alteration, or repair to any building or structure shall require fire protection systems installed per the building code prior to issuance of occupancy. The fire areas as defined by this code of the structure or building not affected by the change of use, addition, alteration, or repair shall comply with the fire suppression system requirements of the building code no later than 10 years from the date of permit issuance for the change of use, addition, alteration, or repair. Prior to the issuance of a permit, the property owner shall enter into a legal agreement with the city that details a plan for the installation of a fire suppression system for the remaining portion of the building. It shall be the applicant's responsibility to pursue said agreement prior to the issuance of the permit. The city of Naperville legal department, fire department and transportation, engineering and development must approve the plan for the installation of the fire suppression system. Exception: Alterations or repairs to improve accessibility, means of egress, or health and sanitation, are not subject to this section. CHAPTER 1 BUILDING CODES
(Ord. No. 02-31, 2-19-2002, eff. 4-8-2002; Ord. No. 06-301, 12-19-2006, eff. 1-1-2007; Ord. No. 07-235, 11-6-2007; Ord. No. 08-056, 3-18-2008; Ord. No. 08-164, 9-2-2008; Ord. No. 10-098, § 1, 8-17-2010; Ord. No. 12-159, § 1(Exh. A), 12-18-2012; Ord. No. 18-096, § 2, 8-21-2018; Ord. No. 18-141, § 2, 12-4-2018; Ord. No. 26-010, § 2, 2-17-2026)
Ask a question about Naperville law
Corpus searches the Naperville sections it holds and shows the ones that match, with their citations. Free, no sign-in.