Section 17F.080.480 Standpipes

Where standpipes are used, the outlet pressure at the top of the riser shall be not less than one hundred PSI provided by a fire pump. Exception: Buildings up to and including five floors above grade (not to exceed 75 feet) will be pressurized by the fire apparatus upon arrival to the site and are not required to provide one hundred PSI at the top outlet of the riser.

Date Passed: Monday, June 16, 2025 Effective Date: Wednesday, July 30, 2025 ORD C36695 Section 8