Sec. 49-1250. - Siphonic roof drainage systems.
A siphonic roof drainage system (SRDS) is an alternative to the roof drainage systems designed in accordance with sections 49-1204, 49-1206, 49-1207 and 49-1211. A siphonic roof drainage system may be installed provided all of the following conditions are met: (a) System shall be designed by a mechanical/plumbing engineer licensed to practice in the State of Nebraska. (b) A structural engineer licensed to practice in the State of Nebraska shall certify that the roof system will support the use of a siphonic roof drainage system. (Certification shall be indicated on the roof drainage plumbing drawings of the contract documents.) (c) Siphonic roof drains shall be provided with domed strainers and conform to section 49-620. (d) Siphonic roof drain design shall be ASPE No. 45-2007 compliant. (e) System shall not be installed when rock is used on the roof unless the inlet contains a rock damn and dome strainer. (f) System shall discharge to daylight, to an area inlet, manhole or a building storm drain, which has been sized for a gravity roof drainage system. (g) Piping system shall be labeled "Siphonic Roof Drainage Line - No modifications without approval from a mechanical/plumbing engineer licensed to practice in the State of Nebraska. Labels shall be placed as required by section 49-512 (or at least once per room). This labeling shall be on the pipe and on the insulation. (h) In addition to labeling required in subsection (g), piping shall be labeled with pipe size and marks at ten-foot increments on all horizontal piping, and with the total horizontal distance marked at the change to vertical. (This is required for inspection purposes to easily verify that piping is installed per drawings.) (i) Siphonic roof drains shall have security screws to prevent removal of inducer and shall include a dome strainer over inducer. (j) The engineer of record shall perform site observation to confirm that siphonic roof drainage system conforms to the contract documents. A copy of the field report shall be submitted to the chief plumbing inspector. (k) The siphonic roof drainage system shall be designed with an independent secondary overflow system. A secondary overflow roof drainage system utilizing roof drains shall be siphonic and shall discharge to daylight per section 49-1210. (l) All materials shall conform to requirements stated elsewhere in this chapter.
(Ord. No. 40524, § 1, 10-20-15)
Ask a question about Omaha law
Corpus searches the Omaha sections it holds and shows the ones that match, with their citations. Free, no sign-in.