Sec. 40-226. - Hydrostatic test.

(a) If the mechanical inspector shall determine that a hydrostatic test is required to determine whether the boiler is safe to carry the pressure allowed, the owner or user of the boiler shall supply the labor, water and pipe connections for such test. The boiler shall be tested at a pressure one and one-half times the pressure to be carried. If, on account of leakage or any other reason, the boiler will not hold this pressure, the owner or user shall have all repairs made as quickly as possible before another test is made. (b) If the second test develops weakness, which in the judgment of the inspector would impair the boiler and not permit the allowed pressure to be carried, he shall condemn the boiler or reduce the pressure allowed to that, which, in his judgment, will be safe.

(Ord. No. 36424, § 1, 10-21-03)