Sec. 7-190. - Testing of backflow prevention devices.

(a) Tests required. Each reduced pressure principle backflow prevention assembly, and double check valve assembly, and pressure vacuum breaker shall be tested immediately after installation, after repairs of any kind, and annually. Any backflow preventer found to be nonfunctional shall be repaired and re-tested within fourteen (14) days of the initial test. (b) Certified testers. Only backflow preventer testers certified by the state department of health shall test backflow preventers located in the water system. (c) Notification. The water system shall notify the owner of each backflow preventer sixty (60) days prior to the date that the backflow preventer is scheduled to be tested.

(Ord. No. 00-0003, § 5, 4-4-00; Ord. No. 19-004, 3-14-19)