Sec. 42-56. - Critical facilities.
Construction of new and substantially improved critical facilities shall be located outside the limits of the special flood hazard area (one percent chance floodplain). Construction of new critical facilities shall be permissible within the SFHA if no feasible alternative site is available. Critical facilities constructed within the SFHA shall have the lowest floor elevated three feet above the base flood elevation at the site (or to the 0.2 percent chance flood elevation whichever is greater). Floodproofing and sealing measures must be implemented to ensure that toxic substances will not be displaced by or released into floodwaters. Access routes elevated to or above the base flood elevation shall be provided to all critical facilities to the maximum extent possible. Critical facilities must not only be protected to the 0.2 percent chance flood, but must remain operable during such an event.
(Ord. No. 2010-10, § 1, 9-21-2010; Ord. No. 2020-13, § 1, 10-6-2020)