§ 15-26-030 — Manufactured gas buildings - Exempted from chapter requirements - When
Municipal Code of Chicago (2026 S-74, current through Council Journal of June 17, 2026) · Municipal Code of Chicago § 15-26-030
Corpus is an independent public-information project, not the official City of Chicago website. Stable reference: corpuslaw.us/code/09d3a149-88dd-45e3-8195-5251a6138c5c
15-26-030 Manufactured gas buildings - Exempted from chapter requirements - When.
Any building used exclusively for the production, distribution, or storage of manufactured gas as a public utility shall be exempt from the requirements of this chapter dealing with construction except the provisions of Section 15-24-170 for tanks for flammable liquids; provided, however, that such buildings shall be Type I or II construction and exterior walls located less than 30 feet from an interior lot line or another building on the same lot and exceeding 45 feet in height shall be of construction providing fire resistance of not less than two hours. (Coun. J. 12-9-92, p. 25465; Amend Coun. J. 2-7-96, p. 15616; Amend Coun. J. 10-7-20, p. 21791, Art. VI, § 51)
Ask a question about Chicago law