For AI agents: read the machine-readable documentation index at /llms.txt or the single-file full reference at /llms-full.txt.

§ 14.04.200 — Section 2308.10.8.1 is added to the 2025 Edition of the California Building Code to read as follows

Pasadena Municipal Code, California (Supp. No. 79: codified through Ordinance No. 7469, enacted May 18, 2026) · Pasadena Municipal Code § 14.04.200

Corpus is an independent public-information project, not the official City of Pasadena website. Stable reference: corpuslaw.us/code/0a5ee303-7601-444c-870a-013e0045d5f7

14.04.200 - Section 2308.10.8.1 is added to the 2025 Edition of the California Building Code to read as follows.

2308.10.8.1 Foundation requirements. Braced wall lines shall be supported by continuous foundations. Exception: For structures with a maximum plan dimension not more than 50 feet (15 240 mm), continuous foundations are required at exterior walls only for structures assigned to Seismic Design Category A, B, or C. For structures in Seismic Design Categories D and E, exterior braced wall panels shall be in the same plane vertically with the foundation or the portion of the structure containing the offset shall be designed in accordance with accepted engineering practice and Section 2308.3.

(Ord. No. 7461, § 5, 11-10-2025)

Ask a question about Pasadena law

Corpus searches the Pasadena sections it holds and shows the ones that match, with their citations. Free, no sign-in.