18.40.220 - Add CBC Section 912.1.1—Design.
Section 912.1.1 is added to Chapter 9 of the California Building Code to read as follows: 912.1.1 Design. Fire Department connections, where required, shall be provided with a minimum number of two (2) 2-½ inch inlets, regardless of the size of the fire sprinkler system. Where fire protection system demands are in excess of 1,000 gpm, a minimum of four (4) 2-½ inch inlets shall be provided. Hazardous locations, high-rise buildings or where fire protection system demands are in excess of 2,000 gpm, a second fire department connection utilizing four (4) 2-½ inch inlets may be required at the discretion of the Fire Code Official.
(ORD-25-0019 § 1(Exh. A), 2025)