For AI agents: read the machine-readable documentation index at /llms.txt or the single-file full reference at /llms-full.txt.

§ 18.40.220 — Add CBC Section 912.1.1—Design

Long Beach Municipal Code (Supp. No. 53, Update 1: codified through Ordinance No. ORD-26-0027, enacted October 13, 2026) · Long Beach Municipal Code § 18.40.220

Corpus is an independent public-information project, not the official City of Long Beach website. Stable reference: corpuslaw.us/code/0a6a54da-288a-4ae9-91fa-da87cc66399b

18.40.220 - Add CBC Section 912.1.1—Design.

Section 912.1.1 is added to Chapter 9 of the California Building Code to read as follows: 912.1.1 Design. Fire Department connections, where required, shall be provided with a minimum number of two (2) 2-½ inch inlets, regardless of the size of the fire sprinkler system. Where fire protection system demands are in excess of 1,000 gpm, a minimum of four (4) 2-½ inch inlets shall be provided. Hazardous locations, high-rise buildings or where fire protection system demands are in excess of 2,000 gpm, a second fire department connection utilizing four (4) 2-½ inch inlets may be required at the discretion of the Fire Code Official.

(ORD-25-0019 § 1(Exh. A), 2025)

Ask a question about Long Beach law

Corpus searches the Long Beach sections it holds and shows the ones that match, with their citations. Free, no sign-in.