§ 225.30

New York City Administrative Code (current through L.L. 2026/147, enacted September 12, 2026, and amendments effective through October 10, 2026) · NYC Electrical Code § 225.30

Corpus is an independent public-information project, not the official City of New York website. Stable reference: corpuslaw.us/code/0b01c6a1-4428-4fd5-a299-760de0b9d773

Section 225.30

Section 225.30 – Revise the opening paragraph in Section 225.30 to read as follows: 225.30 Number of Supplies. Where more than 1 building or other structure is on the same property and under single management, each additional building or other structure that is served by a branch circuit or feeder on the load side of a service disconnecting means shall be supplied by only 1 feeder or branch circuit unless permitted in 225.30(A) through (F). For the purpose of this section, a multiwire branch circuit shall be considered a single circuit.