Sec. 49-1312. - Sizes of stacks equal to area of building drain.

There shall be a vent(s) that terminates through the roof that (originates) from the largest section of the building drain. The following provisions shall apply to stack sizes: (a) The total area of the vent(s) shall be equal to or greater than the area of the largest section of the building drain, (b) The area is not based on the size of the increaser (if required). (c) There shall be a minimum of one three-inch diameter stack in dwelling units provided that the following may apply: (1) A three-inch stack plus a two-inch stack plus a 1½-inch stack will be considered equal to a four-inch stack. (2) Branch vents may be connected to a single increaser. (See Figure 49-1312(c)(2).) _____

(Ord. No. 40524, § 1, 10-20-15)