§ 174.11.03. - Standby power.
Standby power shall be provided to at least one elevator in each bank where the highest floor level of human occupancy is more than 75 feet above the lowest level of fire department vehicle access. Standby power shall be transferable to all other elevators in the bank and shall be capable of operating the elevator with a full load at contract speed. Standby power shall be provided by an approved self-contained generator set to operate whenever there is a loss of power in the normal house current. The generator shall be in a separate room having at least a one-hour fire-resistive occupancy separation from the remainder of the building and shall have a fuel supply adequate to operate the equipment for two hours.
(Ord. No. 838-11-07, § 1(Exh. A), 11-20-07)