§ 254-24. - Lighting and ventilation.
A. Residential.
(1) Habitable rooms.
(a) Every habitable room shall have at least one (1) window or skylight facing directly to the outdoors except as provided hereinafter. The minimum total window area, measured between stops, for every habitable room shall be ten percent (10%) of the floor area or twelve (12) square feet, if the latter area is greater. Whenever the only window in a room is the skylight-type window in the top of such room, the total window area of such skylight shall equal at least fifteen percent (15%) of the total floor area of such room.
(b) Whenever walls or other portions of structures face a window of any such room and such light obstructing structures are located less than three (3) feet from the window and extend to a level above that of the ceiling of the room such a window shall not be deemed to face directly outdoors and shall be included in calculating the required minimum window area.
(c) Every habitable room shall have at least one (1) window or skylight which can be opened easily or such other device as will adequately ventilate the room. The total of openable window area in every habitable room shall be equal to at least fifty percent (50%) of the minimum window area size, as hereinabove provided, except where there is supplied some other approved device affording adequate ventilation.
(d) In any row house constructed prior to 1951 and not used for boardinghouse or lodging house purposes, any interior room not having its own source of natural light and ventilation may be used for living purposes if it contains equivalent artificial means of light [six (6) footcandles per square foot over the area of the room measured thirty (30) inches above floor level at the center of the room] and a mechanical means of ventilation, whose capacity is marked clearly thereon, that provides two (2) air changes per hour or one-half (½) of a cubic foot per minute per square foot for each habitable room other than a kitchen and three (3) air changes per hour, or one and one-half (1 ½) cubic feet per minute per square foot for a kitchen.
(2) Bathrooms and water closet compartments. Every bathroom and water closet compartment shall comply with lighting and ventilation requirements for habitable rooms contained in Subsection A(1) of this section, except that the total window area or skylight area shall be four (4) square feet, not twelve (12) square feet, if this figure is greater than the specified percentage of the total floor area, and with the further exception that no window or skylight shall be required in adequately ventilated bathrooms and water closet compartments equipped with a ventilation system providing at least six (6) air changes per hour or one and one-half (1 ½) cubic feet per minute per square foot, whose capacity is marked clearly thereon, and which is operated either continuously or automatically when the room is in use.
(3) Common spaces other than habitable rooms, bathrooms and water closet compartments.
(a) Every portion of each cellar, furnace room, utility room, hall, landing, staircase and all similar nonhabitable space in a dwelling shall have artificial light available at all times that shall be sufficient to provide an illumination of at least five (5) footcandles; that is, five (5) lumens or one (1) watt per square foot of floor area measured in the darkest portion thereof.
(b) Every portion of any interior or exterior passageway or staircase common to three (3) or more families in a dwelling shall be illuminated at all times with light of at least five (5) footcandles; that is five (5) lumens or one (1) watt per square foot of floor area measured in the darkest portion of the normally traveled stairs and passageways. In dwellings comprising two (2) dwelling units, such illumination shall not be required at all times if separate switches for the control of such light are provided at points convenient and readily accessible to each dwelling unit.
(4) Public passageways.
(a) Every public hall, stairway and passageway in every multiple dwelling, boardinghouse and lodging house shall be ventilated adequately by the natural means specified below or by a ventilating system providing at least one (1) air change per hour [one-fourth (1/4) cubic foot per minute per square foot] and whose capacity is marked clearly thereon.
(b) Any of the specified building types meeting the pertinent standard or standards listed below shall be considered ventilated adequately by natural means:
[1] A building three (3) stories or thirty (30) feet in height or less with front entrance door not less than thirty (30) inches in width and six (6) feet eight (8) inches in height.
[2] A building over three (3) stories or thirty (30) feet in height with hall, stairway and/or passageway window or windows whose total area is equal at least to ten percent (10%) of the total floor area of said hall, stairway and/or passageway.
[3] A building six (6) stories in height or less served by a skylight with a minimum openable area of forty (40) square inches.
(5) Utility spaces. Utility spaces which contain heat producing, air-conditioning and other operating mechanical equipment shall be ventilated to the outer air and air from such spaces shall not be recirculated to other parts of the building.
(6) Special spaces. Natural ventilation of spaces such as attics, basements, cellars and enclosed basementless spaces shall be provided by opening of sufficient space to overcome dampness and minimize the effect of conditions conducive to decay and deterioration of the structure and to prevent excessive heat in attics.
B. Nonresidential.
(1) Occupiable rooms.
(a) Every occupiable room shall contain light transmitting media opening to the sky or on a public street, yard or court that are adequate to provide an average illumination of six (6) footcandles over the area of the room measured at a height of thirty (30) inches above floor level in the center of the room, or an alternate artificial method or device that will provide the equivalent minimum amount of light.
(b) Every occupiable room shall contain ventilating skylights, monitors, louvers, windows, transoms, doors or other natural means of ventilation capable of providing a volume of four (4) air changes per hour [one and one-half (1 ½) cubic feet per minute per square foot] if the room contains less than one thousand (1,000) cubic feet per individual, (2) air changes per hour [one-half (1 ½) cubic feet per minute per square foot] if the room contains one thousand (1,000) cubic feet or more per individual or an alternate mechanical ventilating device, whose capacity is marked clearly thereon, that will provide the equivalent minimum amount of air.
(2) Public passageways. Hallways shall have at least one (1) window opening directly on a street or on a required court or yard in each story, located so that light penetrates the full length of the hallway, with additional windows for each change of direction of the hallway; or the equivalent artificial lighting shall be provided.
(3) Utility spaces. Utility spaces which contain heat producing, air-conditioning and other operating mechanical equipment shall be ventilated to the outer air and air from such spaces shall not be recirculated to other parts of the building.
(4) Special spaces. Natural ventilation of spaces such as basements, cellars, loft areas and enclosed basementless spaces shall be provided by openings of sufficient size to overcome dampness and minimize the effect of conditions conducive to decay and deterioration of the structure and to prevent excessive heat in lofts.