For AI agents: read the machine-readable documentation index at /llms.txt or the single-file full reference at /llms-full.txt.

§ 17.12.945 — Amendment of Section 5003.9 of the 2025 California Fire Code

San José Municipal Code (Supp. No. 5: codified through Ordinance No. 31341, enacted August 25, 2026) · San José Municipal Code § 17.12.945

Corpus is an independent public-information project, not the official City of San Jose website. Stable reference: corpuslaw.us/code/10872bd1-7f30-4101-a0eb-a79ead729515

17.12.945 - Amendment of Section 5003.9 of the 2025 California Fire Code.

Section 5003.9 of the 2025 California Fire Code is amended to read as follows: 5003.9.11 Fire Extinguishing Systems for Workstations Dispensing, Handling, or Using Hazardous Materials. Workstations that can be used for materials with a hazard rating of 3 or 4 in the flammable or reactive category in accordance with NFPA 704 shall be protected by an approved automatic fire extinguishing system in accordance with Section 2703.10. Exception: Internal fire protection is not required for Biological Safety Cabinets that carry NSF/ANSI certification where quantities of flammable liquids in use or storage within the cabinet do not exceed 500 ml.

(Ord. 31258.)

Ask a question about San Jose law

Corpus searches the San Jose sections it holds and shows the ones that match, with their citations. Free, no sign-in.