Sec. 7-194.6. - Grease interceptor design and installation.
(a) Piping design: (1) The inlet and outlet piping shall have 2-way cleanout tees installed. (2) The inlet piping shall enter the receiving chamber above the invert of the outlet piping (2 ⅓" recommended). (3) On the inlet pipe, inside the receiving chamber, a sanitary tee of the same size pipe in the vertical position with the top unplugged shall be provided as a turndown. To provide air circulation and to prevent "air lock", a pipe (nipple) shall be installed in the top of the tee. A pipe installed in the bottom of the tee shall extend to a point of ⅔ depth of the tank. The inlet T should be made of schedule 40 PVC or equivalent material. See illustration. (4) The outlet piping shall be no smaller than the inlet piping, but in no case smaller than four inches (4″) ID. (5) The outlet piping shall extend to twelve inches (12″) above the floor of the interceptor and shall be made of a non-collapsible material. Minimum requirement for outlet piping is schedule 40 PVC. (6) The outlet piping shall contain a tee installed vertically with a pipe (nipple) installed in the top of the tee. Minimum requirement for the outlet tee material is schedule 40 PVC. See illustration. (b) Baffles: (1) The grease interceptor shall have a non-flexing (i.e. concrete, steel, etc.) baffle the full width of the interceptor, sealed to the walls and the floor, and extend from the floor to within a manageable distance from the ceiling (six inches (6″) recommended). The baffle shall have an inverted ninety (90) degree sweep fitting at least equal in diameter size to the inlet piping, but in no case less than six inches (6″) ID. The bottom of the sweep shall be placed in the vertical position in the inlet compartment twelve inches (12″) above the floor. The sweep shall rise to the horizontal portion, which shall extend through the baffle into the outlet compartment. The baffle wall shall be sealed to the sweep. See illustration. (2) The inlet compartment shall be ⅔ of the total liquid capacity with the outlet compartment at ⅓ liquid capacity of the interceptor. (c) Access openings (manholes): (1) Access to grease interceptors shall be provided by a minimum of one (1) manhole per interceptor division (baffle chamber) and of twenty-four-inch (24″) minimum dimensions terminating one inch (1″) above finished grade with cast iron frame and cover. A concrete pad extending a minimum of twelve inches (12″) beyond the outside dimension of the manhole frame shall be provided. One (1) manhole shall be located above the inlet tee hatch and the other manhole shall be located above the outlet tee hatch. A minimum of twenty-four inches (24″) clear opening above each manhole access shall be maintained to facilitate maintenance, cleaning, pumping and inspections. (2) Access openings shall be mechanically sealed and gas tight to contain odors and bacteria and to exclude vermin and ground water, in a manner that permits regular reuse. (3) The manholes are to be accessible for inspection by the city. (d) Additional requirements: (1) Water tightness testing. Precast concrete grease interceptors shall be watertight. A static water test shall be conducted by the city licensed plumber in accordance with the American Society for Testing and Material (ASTM) Standard C1613-10 and timed so as to permit verification through visual inspection by the city. The hydrostatic water test consists of sealing the tank, filling it with water to its operational level, and letting it stand for eight (8) to ten (10) hours. If there is a measurable drop in the water surface, refill the tank to its operational level and let stand for another eight (8) to (10) hours. If there is no further measurable drop in the water surface elevation, the tank passes the test. Tanks shall not be rejected for damp spots on the exterior concrete surface. If the tank fails, it can be repaired and retested. Certification by the licensed plumber, who performs the test, shall be recorded on the Water Tightness Certification Form (Attachment G) and submitted to the city prior to final approval of the GCE. (2) Location. Grease interceptors shall be located so as to be readily accessible for cleaning, maintenance, and inspections. They should be located close to the fixture(s) discharging the greasy wastestream. If possible, grease interceptors should not be installed in "drive-thru" lanes or a parking area. Grease interceptor access manholes shall never be paved over. (3) Cleaning. Grease interceptors shall be cleaned at the frequency of not less than once every ninety (90) days unless approved by the city. Approval will be granted on a case by case basis with submittal by the FSE documenting proof of proposed frequency. Grease interceptors must be pumped-in-full when the total accumulation of surface FOG (including floating solids) and settled solids reaches twenty-five percent (25%) of the grease interceptor's overall liquid depth. This criterion is referred to as the "25 percent rule". Some FSEs may have to pump their grease interceptors on a thirty (30) day or sixty (60) day schedule to meet the twenty-five percent (25%) rule criteria. (4) Responsibility. Removal of the grease from the wastewater routed to a public or private sanitary system is the responsibility of the user. If the user is unresponsive, the responsibility then falls on the property owner. (5) Construction material. Grease interceptors shall be constructed of sound, durable materials, not subject to excessive corrosion or decay, and shall be both water and gas tight. Each interceptor shall be structurally designed to withstand any anticipated load to be placed on the interceptor (i.e. vehicular traffic in parking or driving areas). (6) Standards. Concrete materials and other grease interceptor materials shall meet the appropriate ASTM, the American National Standards Institute, Inc. (ANSI) and International Association of Plumbing and Mechanical Officials (IAPMO) standards. (7) Marking and identification. Prefabricated gravity grease interceptors shall be permanently and legibly marked with the following: a. Manufacturer's name or trademark, or both; b. Model number; c. Capacity; d. Month and year of manufacture; e. Load limits and maximum recommended depth of earth cover in feet; and f. Inlet and outlet. [image omitted; see the official code]
(Ord. No. 18-001, § I, 1-25-18)
Ask a question about Greenville law
Corpus searches the Greenville sections it holds and shows the ones that match, with their citations. Free, no sign-in.