Sec. 114-9. - Cross connection control.
As required by the Mississippi Safe Drinking Water Act and the regulations of the state department of health, it is the purpose of this section to protect the drinking water supplied by the city and to protect the consumers thereof.
(1) Backflow prevention assembly requirement.
a. Elimination and protection of cross connections.
1. Cross connections occurring within the water system shall be eliminated or protected with the appropriate backflow preventer.
2. Cross connections are eliminated by establishing an air gap between the potable and nonpotable sources.
3. Cross connections are protected by installing the appropriate backflow preventer. It shall be the responsibility of the owner of the cross connection to eliminate the cross connection or protect the cross connection with a backflow preventer approved by the water system.
b. Connections to sewer. Direct connections, permanent or temporary, between the water system and a sanitary or storm sewer are prohibited.
c. Home wells prohibited when connected to city water system.
1. In order to avoid potential contamination to the city's water system, it shall be unlawful for any person or entity to construct and/or operate a private well for potable water or irrigation purposes while simultaneously maintaining a connection to the city water system.
2. Any person or entity found to be in violation of this section shall:
i. Have their water service connection terminated until such time as full compliance with EPA, state department of health, and city health regulations has been established to the satisfaction of relevant city authorities; and
ii. May be subject to prosecution and a fine of up to $1,000.00 and/or six months in jail for each such violation.
d. Approved backflow prevention assemblies. Only backflow prevention assemblies approved by the state department of health shall be installed on this water system to comply with this chapter.
e. Installation requirements.
1. Reduced pressure principle assemblies, double check valve assemblies, and pressure vacuum breakers shall be installed in a manner and location that provides adequate access for testing and repair of the assembly.
2. Reduced pressure principle assemblies and double check valve assemblies shall not be subject to possible flooding.
3. Reduced pressure principle assemblies and double check valve assemblies shall not be installed in a pit or enclosure below ground level.
(2) Responsibility of water system.
a. Surveys.
1. An authorized agent of the water system, utilizing written guidelines published by the state department of health, shall conduct surveys and on-site visits as necessary to locate existing cross connections.
2. Single-family dwellings and multifamily dwellings designed to house no more than eight families shall not be included in this survey unless the officials of the water system have reason to believe a cross connection exists.
3. The survey of the water system shall be completed by an individual approved by the water system.
4. Upon completion of this survey, the responsible official of the water system shall certify to the state department of health, on forms provided by the department, that the required survey has been properly performed and completed in accordance with the written guidelines published by the department.
b. Right of entry.
1. The water system, acting through its authorized agent, shall have the right to enter any nonresidential building, during reasonable hours, to inspect the plumbing system installed in any such building or premises provided prior notification of the inspection is given.
2. The authorized agent shall first obtain consent of the owner to enter any single-family dwelling.
c. Classification of hazard. Each cross connection found will be classified as high hazard or low hazard by the authorized agent of the water system.
1. If a connection is found to be a high hazard cross connection, the owner of the connection shall be notified in writing, within ten days, that the cross connection must be eliminated or protected by the installation of a backflow preventer approved by the water system within 90 days of notification.
2. If the connection is found to be a low hazard cross connection, the owner of the connection shall be notified in writing, within ten days, that the connection shall be eliminated or protected by a backflow preventer approved by the water system within one year of notification.
d. Selecting the appropriate backflow preventer.
1. It shall be the responsibility of the water system, acting through its agent, to determine the type of backflow preventer required at each cross connection and the location where the backflow preventer will be installed.
2. The type of backflow preventer and the required installation location will be selected by the water system utilizing guidelines published by the state department of health.
e. Existing backflow preventers. Any backflow prevention device or assembly installed on the water system to protect the water system against the possibility of backflow from a customer's water service prior to the adoption of this chapter shall be governed by this section. Existing backflow preventers shall be inspected and tested within 90 days of identification.
f. Review of meter applications. The water system, acting through its authorized agent, shall review all applications for new meters to determine if a cross connection will be created. The water system shall require the installation of an approved backflow preventer at all new connections where a cross connection will be created.
g. Inspections.
1. The water system, acting through its authorized agent, will periodically inspect any connection to the water system as deemed necessary to insure cross connections have not been created.
2. These inspections may be conducted without prior notice to the customer.
h. Recordkeeping.
1. The water system shall maintain records of the type, size and location of each backflow preventer installed in the system, when each backflow preventer is due to be tested, and the results of each test.
2. Records shall be maintained for five years from the date of the test and inspection.
(3) Testing of backflow prevention devices.
a. Tests required. Each reduced pressure principle backflow prevention assembly, double check valve assembly, and pressure vacuum breaker shall be tested immediately after installation, after repairs of any kind, and annually. Any backflow preventer found to be nonfunctional shall be repaired and retested within 14 days of the initial test.
b. Certified testers. Only backflow preventer testers certified by the state department of health shall test backflow preventers located in the water system.
c. Notification. The water system shall notify the owner of each backflow preventer 30 days prior to the date that the backflow preventer is scheduled to be tested.
(4) Violations and penalties.
a. Refusal of inspection. If the owner refuses to let the authorized agent of the water system perform the necessary inspections to determine if a cross connection exists, the water system shall require that a reduced pressure principle backflow prevention assembly be installed at that service connection.
b. Maintaining a cross connection. If the owner, after having been informed that a cross connection exists at his property, refuses to eliminate or protect the cross connection through the use of the appropriate backflow preventer, water service to the connection shall be terminated until such time as the owner complies with state department of health regulations.
(Code 1968, § 31-9; Ord. No. 1999-9, § 2, 7-6-1999; Ord. No. 2003-5, 6-11-2003)