17.12.470 - Amendment of Section 510.6 of the 2025 California Fire Code.
Section 510.6.1 of the 2025 California Fire Code Section is amended to read as follows: 510.6.1 Testing and proof of compliance. The owner of the building or owner's authorized agent shall have the inbuilding, two-way emergency responder communication coverage system inspected and tested annually or where structural changes occur, including additions or remodels that could materially change the original field performance test. Testing shall consist of the following: 1. In-building coverage test as described in Section 510.5.4. 2. Signal boosters shall be tested to verify that the gain is the same as it was upon initial installation and acceptance or set to optimize the performance of the system. 3. Backup batteries and power supplies shall be tested under load of a period of 1 hour to verify that they will properly operate during an actual power outage. If within the 1-hour test period the battery exhibits symptoms of failure, the test shall be extended for additional 1-hour periods until the integrity of the battery can be determined. 4. All active components shall be checked to verify operation within the manufacturer's specifications. At the conclusion of the testing, a report, which shall verify compliance with Section 510.5.4, shall be submitted to the fire code official. In addition, compliance with 901.6.3.2 shall be mandatory.
(Ord. 31258.)
Ask a question about San Jose law
Corpus searches the San Jose sections it holds and shows the ones that match, with their citations. Free, no sign-in.