Sec. 14-11. - Standpipes.
(a)
This section shall apply to all buildings located within the City of Sarasota which are four (4) or more stories in height and which were not equipped with at least one (1) of the following on January 21, 1985.
(1)
A standpipe riser with a minimum diameter of four (4) inches capable of a minimum flow of two hundred fifty (250) gallons per minute at the roof with a minimum residual pressure of forty (40) pounds per square inch and having a minimum four (4) inch line with a two and one-half (2½) inch fire department connection at street level (at the property line) to pump water into the building.
(2)
A combination standpipe and sprinkler system riser with a minimum diameter of four (4) inches capable of a minimum flow of two hundred fifty (250) gallons per minute at the roof with a minimum residual pressure of forty (40) pounds per square inch and having a minimum four (4) inch line with a two and one-half (2½) inch fire department connection at street level (at the property line) to pump water into the building.
(b)
The owner of a building to which this section applies shall be required to install a standpipe riser in the building with a minimum diameter of four (4) inches which is capable of producing a minimum flow of two hundred fifty (250) GPM at the roof with a minimum residual pressure of 40 PSI and which has a minimum four (4) inch line with a two and one-half (2½) inch fire department connection at street level at the property line. Each intermediate floor shall have an outlet equipped with an approved hose valve for attachment of hose with an easily removable two and one-half (2½) inch by one and one-half (1½) inch reducer suitable for Class III service.
(c)
The owner of a building to which this section applies shall further be required to install a new fire pump or to increase the size of the existing fire pump whenever same is necessary to meet the minimum gallonage and pressure requirements specified in paragraph (b), above. New or larger fire pumps installed pursuant to this paragraph shall not be required to be connected to the emergency system as required by Section 700-12 of the City of Sarasota amendments to the National Electric Code, 1987 edition. In the event a new or larger fire pump installed pursuant to this section would require the installation of a new generator or an increase in the existing generator size in order to operate the fire pump; then such fire pumps may be wired ahead of the main building disconnect.
(d)
Nothing herein shall be construed to require that standpipes installed pursuant to this ordinance shall comply with Section 902.3.1 of the City of Sarasota amendments to the 1985 edition of the Standard Building Code, with 1986 accumulated revisions thereto.
(e)
Installation of standpipe risers as required by this section shall be completed in accordance with the following schedule. All time periods specified herein shall commence on July 20, 1987.
(1)
Buildings with five (5) or more stories .....2 years
(2)
Buildings with four (4) stories .....3 years
The above time periods may be extended by the fire official as provided for in section 14-13, hereof.
(f)
In buildings equipped with an automatic sprinkler system, the city manager, or his designee, may grant an exemption from the provisions of this section upon the written request of owner of a building to which this section applies. The written request shall:
(1)
Be submitted to the city manager, or his designee.
(2)
Be supported with a signed statement from a licensed engineer, bearing the engineer's official seal, which certifies the design and fire flow calculations for the automatic sprinkler system installed in the subject building.
(3)
Be supported by a signed statement from an automatic sprinkler contractor, duly authorized to do business in the State of Florida, which certifies that: The automatic sprinkler system meets all the requirements of NFPA 13, 1985 edition, or the current edition of that code in effect at the time that the request for the exemption is submitted; that the automatic sprinkler system has been tested and inspected, by said sprinkler contractor; and that based upon the inspection and test the sprinkler system is complete and in proper working order.
When the city manager, or his designee, has determined the sufficiency of the statements from the owners' engineer and sprinkler contractor, the city manager, or his designee, shall then determine whether the building incorporates an exit system which meets all the requirements of the Life Safety Code NFPA-101, 1985 edition, or such edition of said code as is in full force and effect at the time of the request for the exemption. When the city manager, or his designee, has determined that the owner has met the requirements, set forth in this subsection, the exemption shall be granted.
(Ord. No. 89-3338, § 1, 10-2-89; Ord. No. 95-3864, § 2, 2-5-96)