Sec. 43-322. - Special requirements for bed and breakfast occupancies.

The following special requirements must be met, to the extent possible for historic structures listed on the local or national register, as required in section 55-765 of this Code: (a) A full time monitored fire alarm system must be installed and operational at all times. (b) All exits in common areas must be clearly identified with illuminated exit signs. (c) Fire alarm pull stations shall be provided at all exit locations and hallways of sleeping rooms. (d) Emergency egress lighting with a battery backup must be installed as per manufacturer's instructions in order to provide a minimum of one foot candle illumination three feet above the floor. (e) All first time occupancies shall install an NFPA approved 13R fire sprinkler system in addition to the alarm system.

(Ord. No. 40326, § 2, 4-21-15)