§ 55-96 — Industrial backflow
Code of Ordinances, City of Corpus Christi, Texas (Supp. No. 44: codified through Ordinance No. 033940, enacted June 2, 2026) · Corpus Christi Code of Ordinances § 55-96
Corpus is an independent public-information project, not the official City of Corpus Christi website. Stable reference: corpuslaw.us/code/1e2bd87d-9e6b-487d-9521-f6beb9c330e5
Sec. 55-96. - Industrial backflow.
(a) All potable water connections between an industrial facility or industrial processing unit and the city's water system must be equipped with a reduced pressure backflow preventer (assembly) or air gap, which will prevent backflow and back-siphonage. A reduced pressure backflow preventer (assembly) or air gap must be installed directly after each city meter servicing potable water and meet Texas Commission on Environmental Quality and Municipal Code requirements. If an industrial facility is in compliance with all TCEQ regulations related to backflow prevention, the city's chief operating officer may, at his discretion and in writing, approve the facility's use of a backflow prevention method that is an alternative to the reduced pressure backflow preventer (assembly) or air gap, is in addition to fully-effective cross-connection control in accordance with TCEQ requirements, and is fully verifiable by the city at or adjacent to each city meter. Approval of such system requires a chief operating officer determination that such system provides better protection of the city's water system than a reduced pressure backflow preventer (assembly) or air gap. (b) Fire service lines must have a double-check assembly directly after the city meter or tap. (c) All backflow preventers (assemblies), excluding air gaps, must be inspected and certified to be operating within specifications on an annual basis by a state-licensed backflow prevention assembly tester. In addition, the backflow prevention assembly tester must file a copy of the test report with the city's third-party database within ten (10) days of the testing. (d) Upon installing, repairing, or replacing a reduced pressure backflow preventer (assembly) or an air gap on a property with an industrial facility or industrial processing unit, an industrial district affidavit must be immediately submitted by a Texas licensed professional engineer to the utilities department for each city water meter on the property. In addition, upon relocating a water meter, an industrial district affidavit must be immediately submitted by a Texas licensed professional engineer to the utilities department. The industrial district affidavit must confirm there is no cross-connection between the city meter(s) and backflow preventer(s) and will be on a form designated by the city. The industrial district affidavit also identifies the location of each backflow preventer(s). (e) The city has the right to inspect any connections to the city's water system, including any valves and backflow prevention devices. (f) If the owner or operator of an industrial facility or industrial processing unit fails to comply with this section, the city may refuse to connect the industrial facility or industrial processing unit or disconnect the property, facility, or unit from the city's water supply system. Failure to comply with the requirements of this section will result in termination of the water service. (g) A violation of this section is a nuisance punishable by a fine of up to two thousand dollars ($2,000.00). Each day any violation of this section continues constitutes a separate offense. (h) If an industrial facility is in compliance with all TCEQ regulations related to backflow prevention as of the effective date of the ordinance codified in this section, then the chief operating officer of the city may, at his discretion and in writing, provide the facility a time period of up to one hundred eighty (180) days to bring the facility into compliance. Regardless of any time period provided for compliance with this section, if an imminent threat to the city's water system exists, the city will terminate the customer's water service immediately.
(Ord. No. 032617, § 1, 12-7-2021)
Ask a question about Corpus Christi law
Corpus searches the Corpus Christi sections it holds and shows the ones that match, with their citations. Free, no sign-in.