Sec. 49-1143. - Type II interceptors for non-flammable waste.
Type II non-flammable interceptors shall be installed as follows: (a) Shall be minimum 24 inches inside diameter and 36 inches deep and shall have a minimum depth below the water level of 24 inches. (b) Constructed of cast iron or 3,000 pound rated, formed concrete with a minimum reinforced wall thickness of four inches; or Reinforced concrete pipe. (c) Shall have a cover designed to withstand traffic loads. (d) Shall have a minimum trap seal of eight inches with a full size cleanout. (e) Shall have a four inch, independent vent through the roof. (f) Shall have at least four-inch inlet and outlet waste connections. (See Figure 49-1143.)
(Ord. No. 40524, § 1, 10-20-15)