§ 14X-5-504.2.9 — High-rise buildings
Municipal Code of Chicago (2026 S-74, current through Council Journal of June 17, 2026) · Municipal Code of Chicago § 14X-5-504.2.9
Corpus is an independent public-information project, not the official City of Chicago website. Stable reference: corpuslaw.us/code/215d9757-b719-44ce-b949-5f8fe949dac4
14X-5-504.2.9 High-rise buildings.
An automatic sprinkler system must be provided throughout high-rise buildings. Exceptions: 1. Parking facilities complying with Section 406 of the Chicago Building Code. 2. Open-air portions of a Group A-5 occupancy. 3. A building of Group R-2 occupancy, together with any accessory occupancies complying with Section 508.2 of the Chicago Building Code and any attached parking garage that is used exclusively by the building’s non-transient residential occupants and their guests or by persons who, pursuant to a written lease agreement, rent a parking space in time increments of at least one month. 4. The following portions of a mixed-occupancy building where separated from other occupancies by construction having a fire-resistance rating of not less than 2 hours: 4.1. Any portion classified as Group R-2 occupancy. 4.2. Any accessory occupancy connected to the Group R-2 occupancy and complying with Section 508.2 of the Chicago Building Code. 4.3. A parking garage that is used exclusively by the building’s non-transient residential occupants and their guests or by persons who, pursuant to a written lease agreement, rent a parking space in time increments of at least one month. 4.4. In buildings of Type I construction, non-residential occupancies located not more than 80 feet (24.4 m) above grade that are separated in accordance with Section 508.4 of the Chicago Building Code and that cumulatively do not exceed 10% of the floor area of the Group R-2 occupancy in the building. 5. A Chicago Landmark, unless the building is required to be equipped with an automatic sprinkler system by another provision of the Municipal Code. 6. A building color-coded red or orange in the Chicago Historic Resources Survey, published in 1996, unless the building is required to be equipped with an automatic sprinkler system by another provision of the Municipal Code.
Ask a question about Chicago law
Corpus searches the Chicago sections it holds and shows the ones that match, with their citations. Free, no sign-in.