Sec. 49-1531. - Minimum design standard.
All water supply systems (except where noted in section 49-1533) shall meet the following minimum design standards under conditions of peak demand: (a) Pipe size based on no more than six pounds pressure drop per 100 feet. (b) Velocity for cold water shall not exceed eight feet per second (fps). Velocity for hot water 140 degrees Fahrenheit or less shall not exceed five feet per second (fps). Water temperatures exceeding 140 degrees Fahrenheit shall not exceed three feet per second (fps) velocity. (c) Maximum fixture units based on section 49-1530. (d) Water meter pressure drop of not more than 15 psig. (e) Residual pressure required at fixture: (1) Flush tank = 15 psig. (2) Flush valve = 25 psig. (3) Other fixtures = 8 psig. A water pressure booster system shall be installed whenever the main pressure is insufficient to provide residual pressure at a fixture outlet (see section 49-1532). Size of domestic water run outs to single fixtures may match the connection size for the fixture. Such runs shall be a minimum one-half inch.
(Ord. No. 40524, § 1, 10-20-15)