For AI agents: read the machine-readable documentation index at /llms.txt or the single-file full reference at /llms-full.txt.

MC 1010 — Gauges

New York City Administrative Code (current through L.L. 2026/147, enacted September 12, 2026, and amendments effective through October 10, 2026) · NYC Mechanical Code § MC 1010

Corpus is an independent public-information project, not the official City of New York website. Stable reference: corpuslaw.us/code/25104463-7406-4345-8766-6ccd71930e9f

Section MC 1010: Gauges

1010.1 Hot water boiler gauges. Every hot water boiler shall have a pressure gauge and a temperature gauge, or a combination pressure and temperature gauge. The gauges shall indicate the temperature and pressure within the normal range of the system's operation. 1010.2 Steam boiler gauges. Every steam boiler shall have a water-gauge glass and a pressure gauge with a siphon. The pressure gauge shall indicate the pressure within the normal range of the system's operation. 1010.2.1 Water-gauge glass. The gauge glass shall be installed in accordance with the ASME Boiler and Pressure Vessel Code or ASME CSD-1.