18-99 Smoke detectors.
(a) Each and every dwelling, rooming house, dwelling unit or rooming unit let to another for occupancy shall meet the following requirements for smoke detectors/alarms.
(1) Smoke detectors/alarms shall be installed in the following, areas:
a. In every sleeping room or area;
b. Outside every sleeping room or area in the immediate vicinity of the sleeping room or area; and
c. On all levels of the dwelling, dwelling unit, rooming house, or rooming unit, including basements but excluding crawl spaces and unfinished attics.
d. Notwithstanding the above installation locations, detectors/alarms shall not be located within kitchens or garages or in other spaces where temperatures can fall below forty (40) degrees F (four (4) degrees C) or exceed one hundred (100) degrees F (thirty-eight (38) degrees C). Detectors/alarms shall not, unless specifically listed for the application, be located closer than three (3) feet (0.9 m) horizontally from:
1. The door to a kitchen.
2. The door to a bathroom containing a tub or shower.
3. The supply registers of a forced air heating or cooling system, and outside of the airflow from those registers.
(2) Smoke detectors/alarms shall receive their operating power from the building electrical system but shall also receive power from a battery when the building electrical system power is interrupted.
(3) Smoke detectors/alarms within each dwelling unit or rooming unit shall be interconnected so that the sensing of smoke by one detector sounds the alarms of all detectors within that dwelling unit or rooming unit.
(4) Smoke detectors/alarms shall be approved or listed by a nationally recognize testing or listing agency for the purposes for which they are intended.
(5) Smoke detectors/alarms shall be properly installed and shall be maintained in good working condition.
(b) All other dwellings, rooming houses, dwelling units or rooming units not covered by (a) shall have a smoke detector/alarm installed adjacent to bedroom areas. Such smoke detectors/alarms shall be approved or listed by a nationally recognized testing or listing agency for the purposes for which they are intended.
(c) Effective date. Unless an extension is granted by the Burlington Code Enforcement Office pursuant to subsection (d) of this section, the provisions of section 18-99(a) shall take effect on May 31, 2004. Between the effective date of this subsection (c) and May 31, 2004 and during the period of any extension granted pursuant to subsection (d), the provisions of subsection (b) shall apply to all dwellings, rooming houses, dwelling units, and rooming units whether or not they are let to another for occupancy.
(d) Procedure to request extension of effective date. If the owner of one or more dwellings, rooming houses, dwelling units or rooming units let to another for occupancy files with the Burlington Code Enforcement Office:
(1) A certification that all of such units, dwellings and houses owned by the owner in the City of Burlington presently contain and shall continue to contain for the period of implementation smoke detectors which are approved or listed by a nationally recognized testing or listing agency; and
(2) A certification that all of the smoke detectors referred to in clause (1) are presently properly installed and shall continue to be so for the period of implementation in accordance with manufacturer’s specifications adjacent to all bedroom areas on each level of the applicable buildings and are operating and maintained in good working condition and shall continue to be so for the period of implementation; and
(3) A written plan of implementation pursuant to which all units owned by the owner within the City of Burlington shall be brought into compliance with section 18-99(a) over time, but not later than May 31, 2007, then, subject to the approval of the Burlington Code Enforcement Office, as described below, implementation of section 18-99(a) shall take place in accordance with the plan of implementation on or before May 31, 2007 with respect to the building(s) for which the certification and plan have been provided.
The submission of a written plan accompanied by the smoke detector certifications shall stay the enforcement of the provisions of section 18-99(a) with respect to the units identified in the plan, pending approval or denial of the request for an extension. The Burlington Code Enforcement Office shall approve in writing the extended implementation date set forth in the written plan for any owner that reasonably satisfies the requirements of this subsection and subsection (e). Failure of the code enforcement office to approve, deny, or request further information from an owner in response to a request for an extended implementation date submitted in accordance with the provisions of this subsection and subsection (e) within 60 days of the date of such submission, or within sixty (60) days of the submission of the additional information requested by the code office, shall be deemed to constitute an approval of the extended implementation date and the owner shall carry out the implementation plan described in subsection (3), above.
(e) Implementation plan requirements; denial of extension. An implementation plan described in subsection (d)(3) shall, at a minimum, include a statement of need for the extension, a cost estimate for compliance, and a timeline for all units to be in compliance, with benchmarks, phasing, and any other relevant details. In addition to a denial based upon a failure to comply with the requirements of this subsection or subsection (d), a request to extend implementation for all units subject to such request may be denied should the code office determine with respect to any unit for which an extension has been requested: (i) that violations of one or more minimum housing fire division standards exist in the unit or (ii) that there is an outstanding order by fire code enforcement officials for the unit, or (iii) the owner has failed to comply with two (2) or more unappealed orders issued during the previous three (3) years by either fire or housing code enforcement officials and that in each such instance, the owner was not granted an extension for compliance, or (iv) any other specific and identified condition or conditions related to fire safety in the unit which pose(s) a substantial and immediate risk to the safety of persons or property. Except as provided in clause (3), a request to extend implementation may be renewed following resolution of such outstanding violation or order.
(f) Procedure to request equivalent systems.
(1) At any time, an owner of a dwelling, rooming house, dwelling unit or rooming unit let to another for occupancy may request the code office to grant the owner an exception, an alternative, an equivalent system or a variance from the requirements of section 18-99(a). Any such request for an exception, alternative, equivalent system or variance shall be made in writing and shall be based upon either a current or a proposed system for smoke or fire detection within the dwelling, rooming house, dwelling unit or rooming unit.
(2) A request for approval of an exception, alternative, equivalent system or variance shall be granted to the owner by the code enforcement office if the owner demonstrates that the existing or proposed smoke detector system complies with the applicable provisions of the smoke detection protocols established by the code enforcement office pursuant to section 18-25A of the Ordinances and subsection (g) of this section 18-99. The Code Enforcement Office shall respond to the request in writing within 30 days and shall either approve or deny an exception, an alternative, an equivalent system or a variance. The office’s response shall provide the applicant with a written explanation for any denial of the application, with specific reference to the facts and to the applicable smoke detection protocols.
(3) An owner may appeal the office’s denial or approval with conditions by filing a written appeal with the chief of the code enforcement office within thirty (30) days of the date of the written decision. The appeal shall specifically state the reasons why the owner believes that the office’s decision was erroneous, and shall make specific reference to the smoke detector protocols. The chief of the code enforcement office shall issue a written decision on the appeal or shall request additional information within thirty (30) days of the date of the appeal. A denial of the appeal by the chief of the code enforcement office shall contain a written explanation for the denial and shall specify the facts and the protocols upon which the decision is based. If no decision is made within thirty (30) days of the appeal or, if applicable, within thirty (30) days of the date that the requested additional information is received, the original application of the owner shall be deemed to be approved.
(4) Nothing in this subsection 18-99(d) shall be deemed to limit the right of an owner to pursue an appeal under section 18-94 of the Ordinances, provided that such an appeal may not be filed unless an appeal has first been denied in whole or in part by the Chief of the Code Enforcement Office pursuant to this subsection (f) of section 18-99
(g) Smoke detector protocols. The code enforcement office shall, not later than May 31, 2003, adopt an initial set of smoke detection protocols which establish criteria for exceptions, alternatives, equivalent systems and variances from the requirements of section 18-99(a). Such protocols may adopt by reference the forms of equivalency found in Burlington’s adopted fire and building codes and shall provide an equal or greater level of safety to that set forth by the requirements of section 18-99(a). The adoption of smoke detection protocols shall conform to the procedures required in section 18-25A for the adoption of protocols for exceptions, alternatives, equivalent systems and variances from the strict provisions of Chapter 18 (Housing) of these ordinances.
(h) Penalties. Notwithstanding section 18-31 of the Burlington Ordinances, any person who intentionally disconnects or otherwise disables a smoke detector installed and maintained in accordance with the provisions of this section shall be subject to a civil fine of not less than two hundred dollars ($200.00) and not more than five hundred dollars ($500.00), with a waiver penalty of one hundred fifty dollars ($150.00). If a smoke detector is disconnected or disabled, that fact shall create a rebuttable presumption that the adult occupants of the dwelling unit were responsible for the act of disconnecting or disabling the smoke detector.