For AI agents: read the machine-readable documentation index at /llms.txt or the single-file full reference at /llms-full.txt.

§ 609 — HEALTH CARE PLUMBING

The Philadelphia Code (2026 Code: The Philadelphia Code and Home Rule Charter current through October 8, 2026) · Philadelphia Code Subcode P, § 609

Corpus is an independent public-information project, not the official City of Philadelphia website. Stable reference: corpuslaw.us/code/28b4764e-6a75-4992-8e13-b69284f918e1

SECTION 609 HEALTH CARE PLUMBING

* * * P-609.2 Water service and distribution for Group I-2, Condition 2 facilities. Hospitals Group I-2, Condition 2 facilities shall have not fewer than two water service pipes and water distribution pipes sized such that with the loss of the largest service pipe, the remaining service pipes will meet the water demand for the entire facility. Each water service shall have a shutoff valve in the building and a shutoff valve at the utility-provided point of connection to the water main or other source of potable water. * * *

Ask a question about Philadelphia law

Corpus searches the Philadelphia sections it holds and shows the ones that match, with their citations. Free, no sign-in.