SECTION 609 HEALTH CARE PLUMBING
* * * P-609.2 Water service and distribution for Group I-2, Condition 2 facilities. Hospitals Group I-2, Condition 2 facilities shall have not fewer than two water service pipes and water distribution pipes sized such that with the loss of the largest service pipe, the remaining service pipes will meet the water demand for the entire facility. Each water service shall have a shutoff valve in the building and a shutoff valve at the utility-provided point of connection to the water main or other source of potable water. * * *