Same—Amendments.
New Orleans City Code § 26-17
in effectSec. 26-17. - Same—Amendments.
Chapter 1 of the International Mechanical Code, 2021 Edition, shall be deleted in its entirety, and the following shall be substituted in lieu thereof:
CHAPTER 1
ADMINISTRATION
SECTION 101 - GENERAL
101.1 - Title. These regulations shall be known as The International Mechanical Code, 2021 Edition, as amended by the City of New Orleans hereinafter referred to as "this code."
The Director of the Department of Safety and Permits, as the appointing authority of the Department, and all of its Divisions, is hereinafter referred to in this code as "the Director."
101.2 - Scope. The provisions of this code regulate the design, installation, maintenance, alteration and inspection of mechanical systems that are permanently installed and utilized to provide control of environmental conditions and related processes within buildings. This code shall also regulate those mechanical systems, system components, mechanical appliances, the stationary equipment, and the hoisting and portable equipment specifically addressed herein. The installation of fuel gas distribution piping and equipment, fuel gas-fired appliances and fuel gas-fired appliance venting systems shall be regulated by the International Fuel Gas Code.
101.2.1 - Appendices. Provisions in the appendices shall not apply unless specifically adopted.
101.3 - Intent. The purpose of this code is to provide minimum standards to provide a reasonable level of safety, to protect the health and general welfare of the public and property, by regulating and controlling the design, construction, installation, quality of materials, location, operation and maintenance or use of mechanical systems and by the certification of the operators of the equipment specified herein.
101.3.1 - Quality Control. Quality control of materials and workmanship is not within the purview of this Code except as it relates to the purposes stated herein.
101.4 - Severability or partial invalidity. In the event any section, subsection, sentence, clause, phrase or portion of this code is, for any reason, held to be unconstitutional, illegal or void, such decision shall not affect the validity of the any of the remaining portions of this code.
SECTION 102 - APPLICABILITY
102.1 - General. Where, in a specific case, different sections of this code specify different materials, methods of construction or other requirements, the most restrictive shall govern. Where there is a conflict between a general requirement and a specific requirement, the specific requirement shall be applicable.
102.1.1 - Other Laws. The provisions of this code shall not be deemed to nullify any provisions of local, state or federal law.
102.2 - Existing installations. Except as otherwise provided for in this Chapter, no provision in this code shall require the removal, alteration or abandonment of, nor prevent the continued utilization and maintenance of, a mechanical system or mechanical equipment lawfully in existence at the time of the adoption of this code.
102.3 - Maintenance. Mechanical systems, both existing and new and parts thereof shall be maintained in proper operating condition in accordance with the original design and in a safe and sanitary condition. Devices or safeguards which are required by this code shall be maintained in compliance with the code edition under which they were installed. The owner or the owner's authorized agent shall be responsible for maintenance of the mechanical systems. To determine compliance with this provision, the Director has the authority to require the mechanical system to be reinspected.
102.4 - Additions, alterations or repairs. Additions, alterations, renovations or repairs to a mechanical system shall conform to that required for a new mechanical system without requiring the existing mechanical system to comply with all of the requirements of this code. Additions, alterations or repairs shall not cause an existing mechanical system to become unsafe, hazardous or overloaded.
Minor additions, alterations, renovations and repairs to existing mechanical systems shall meet the provisions for new construction, unless such work is done in the same manner and arrangement as was in the existing system, is not hazardous and is approved.
102.5 - Change in occupancy. It is unlawful to make a change in the occupancy of any structure which will subject the structure to any special provisions of this code applicable to the new occupancy without approval. The Director shall certify that such structure meets the intent of the provisions of law governing building construction for the proposed new occupancy and that such change of occupancy does not result in any hazard to the public health, safety or welfare.
102.6 - Historic buildings. The provisions of this code relating to the construction, alteration, repair, enlargement, restoration, relocation or moving of buildings or structures shall not be mandatory for existing buildings or structures identified and classified by the state or local jurisdiction as historic buildings when such buildings or structures are judged by the Director to be safe and in the public interest of health, safety and welfare regarding any proposed construction, alteration, repair, enlargement, restoration, relocation or moving of buildings.
102.7 - Moved buildings. Except as determined by Section 102.2, mechanical systems that are a part of buildings or structures moved into or within the jurisdiction shall comply with the provisions of this code for new installations.
102.8 - Referenced codes and standards. The codes and standards referenced herein shall be those that are listed in Chapter 15 and such codes and standards shall be considered as part of the requirements of this code to the prescribed extent of each such reference. Where differences occur between provisions of this code and the referenced standards, the provisions of this code shall apply.
102.9 - Requirements not covered by this code. Requirements necessary for the strength, stability or proper operation of an existing or proposed mechanical system, or for the public safety, health and general welfare, not specifically covered by this code, shall be determined by the Director.
SECTION 103 - DUTIES AND POWERS
103.1 - General. The Director of the Department of Safety and Permits is hereby authorized and directed to enforce the provisions of this code. The Director shall have the authority to render interpretations of this code and to adopt policies and procedures in order to clarify the application of its provisions. The interpretations, policies and procedures shall be in compliance with the intent and purpose of this code. The interpretations, policies and procedures shall not have the effect of waiving requirements specifically provided for in this code.
103.2 - Records. The Director shall keep, or cause to be kept, a record of the business of the Department in accordance with the public record law of the State of Louisiana.
103.3 - Application and Permits. The Director shall receive applications, review construction documents and issue permits for the installation and alteration of mechanical systems, inspect the premises for which the permits have been issued and enforce compliance with the provisions of this code.
103.4 - Notices and Orders. The Director shall issue all necessary notices or orders to ensure compliance with this code.
103.5 - Inspections. The Director shall make all of the required inspections, or shall accept reports of inspections by approved agencies or individuals, in a manner deemed appropriate by the Director and subject to regulation as provided in the New Orleans Amendments to the International Building Code or through written administrative policy. All reports of inspections shall be in writing and be certified by a responsible officer of such approved agency or by the responsible individual. The Director is authorized to engage such expert opinion as deemed necessary to report upon unusual technical issues that arise, subject to the approval of the appointing authority.
103.6 - Identification. The Director shall carry proper identification when inspecting structures or premises in the performance of duties under this code.
103.7 - Right of Entry. When it is necessary to make an inspection to enforce the provisions of this code, or when the Director has reasonable cause to believe that there exists, in a structure or upon any premises, a condition which is contrary to or in violations of this code which makes the structure or premises unsafe, dangerous or hazardous, the Director is authorized to enter the structure or premises at all reasonable times to inspect or to perform the duties imposed upon him by this code. If such structure or premises is occupied, the Director shall present credentials to the occupant and request entry. If such structure or premises is unoccupied, the Director shall first make a reasonable effort to locate the owner or other person having charge or control of the structure or premises and request entry. If entry is refused, the Director has recourse to every remedy provided by law to secure entry.
103.8 - Liability. The Director, designee or any employee charged with the enforcement of this code, while acting for the jurisdiction in good faith and without malice in the discharge of the duties required by this code or other pertinent law or ordinance, shall not thereby be rendered civilly liable personally, and is hereby relieved from personal liability for any damage accruing to persons or property as a result of any act or be reason of an act or omission in the discharge of official duties.
Any suit instituted against any officer or employee because of an act performed by that officer or employee in the lawful discharge of his duties and under the provisions of this code shall be defended by the legal representative for the Department of Safety and Permits until the final termination of the proceedings. The Director or any of his subordinates shall not be liable for costs in an action, suit or proceeding that is instituted in pursuance of the provisions of this code; and any officer in the Mechanical Inspection Division, acting in good faith and without malice, shall be free from liability for acts performed under any of its provisions or by reason of any act of inclusion or omission in the performance of official duties as required by this code.
SECTION 104 - PERMIT AND FEE REQUIREMENTS
104.1 - Permit Required - A permit is required to erect, install, enlarge, alter, repair, remove, convert or replace a mechanical system, the installation of which is regulated by this code. No work may commence until the required permit is issued except where the work must be performed in an emergency situation.
Exceptions: (1) approved self-contained refrigeration equipment up to 1 H.P.; (2) approved self-contained factory-built air conditioning unit, commonly referred to as "window unit," used in private residences and without ducts, (providing the air conditioning unit does not project over public property).
104.2 - Permit Applications. Each permit application, with the required fee, shall be filed with the Mechanical Inspection Division on a form furnished for that purpose and shall contain a description of the proposed work and its location. An application must be filed by a Class "A" Air Conditioning and Refrigeration Contractor with an active license and must be signed by the license holder.
104.3 - Permit Validity - Each permit application must be properly completed with the signature of the license holder, and the proper fees paid, before being processed, approved and assigned a formal mechanical permit number.
No work may commence until the permit application is approved and issued by the Mechanical Inspection Division except when failure to commence the work would be life threatening or the work is an emergency due to disaster or any uncontrolled event or occurrence.
A permit shall be construed to be authorization to proceed with the work and shall not be construed as authority to violate, cancel, alter, or set aside any of the provisions of this Code, or any other ordinances adopted by the City of New Orleans, including the Comprehensive Zoning Ordinance nor shall such issuance of a permit prevent the Director from thereafter requiring a correction of errors in the Construction Documents or in the installation, construction, or of violations of this Code.
104.4 - Permit Expiration. Every permit issued shall expire if the work authorized by such permit does not commence within six (6) months after the date of its issuance, or if the work authorized by such permit is suspended for more than six (6) months after the date of its issuance, or if the work authorized by such permit is suspended or discontinued for a period of six (6) months after the date the work began. One or more extensions of time may be allowed for the permit provided the extension is requested in writing and justifiable cause is demonstrated to the Director. When the Director grants an extension, it shall be in writing to the requestor, and the period shall not exceed ninety (90) days each.
104.5 - Permit Fees. Installations, reinstallations, alterations, or replacement or addition of prime movers (condensers) shall pay the fees listed below:
From 1 to 3 Tons .....$15.00
For each Ton over 3 Ton .....$ 3.00
Cooling towers
1 to 50 tons .....$40.00
51 tons to 100 tons .....$65.00
Over 100 tons .....$85.00
Additional fees for the associated gas and/or electric heating units are listed on the Mechanical Inspection Division Permit Application form.
The total fee for any work begun prior to obtaining the required permit, excepting the emergency or life threatening conditions, shall be the listed fee plus a penalty fee of five (5) times the listed fee for such work.
104.6 - Alteration Permits. Alteration permits fees shall be based on contract price at a rate of $30.00 for the first $1,500.00 of cost or part thereof plus $10.00 for each additional $1,000.00 or part thereof.
104.7 - Definitions. For purposes of definitions under this Code,
1. One (1) Ton shall be considered to be equal to or less than 12,000 Btu per hour.
2. 3,413 Btu shall be considered equal to one (1) KW.
3. One boiler horsepower shall be considered equal to 33,465 Btu per hour.
4. Hot Water Boilers: Any vessel in which water is heated, steam is generated, steam is superheated, or any combination thereof, under pressure or vacuum for use external to itself, by the direct application of heat, that is heat resulting from the combustion of fuel, electrical elements, nuclear fuel, or waste gasses.
SECTION 105 - CONSTRUCTION DOCUMENTS
Construction Documents involving mechanical installations are to be submitted at the time of application for building permits. See Article 106 - Construction Documents of the New Orleans Amendments to the International Building Code for details.
SECTION 106 - ANNUAL INSPECTION AND FEES
106.1 - All Air Conditioning systems and Water Heaters in commercial and industrial installations shall be subject to inspections for installation safety by the Mechanical Inspection Division according to the following schedules and fees:
ANNUAL INSPECTIONS FEE
Commercial and Industrial Installations
Refrigeration and/or Air Conditioning systems (up to 99 tons) …$15.00/system
Refrigeration and/or Air Conditioning systems (100 or more tons) …$35.00/system
Cooling Towers…$20.00/system
Water Heaters …$10.00/system
Generators …$15.00/system
106.2 - All inspection fees are due and payable upon receipt of the "ANNUAL INSPECTION MECHANICAL EQUIPMENT" bill. Fees will be doubled after 30 days if bill remains unpaid. After 60 days action will be taken to have the utilities disconnected until payment and/or corrections has been received.
106.3 - Inspections And Posting.
106.4. Installation Inspection. The installer of every Class A, B or C system shall notify the Director not less than 36 hours prior to the day on which the installations are to be inspected. Failure to notify the Director as required shall be deemed a violation of this Code. The Director shall make all inspections promptly, and shall issue within 72 hours of inspection, a Certificate of Approval to the installer upon satisfactory completion of such inspections. Saturdays, Sundays and holidays shall not be included in this 72 hour period. Inspections of installations in any building or facility shall be made before the piping and connections of the system are covered and/or made inaccessible.
106.5 - Biennial Inspections And Fees.
106.5.1. Upon approval of the Director, an owner may elect to have all equipment listed in 106.1 to 106.4 inspected every two years in lieu of an annual inspection. This biennial inspection shall not be applicable to any equipment, systems, building, structure or plant that requires a building safety summary or an attending stationary engineer. The fees associated with a biennial inspection shall be twice those listed in Section 106.1.
SECTION 107 - CERTIFICATES OF APPROVAL
The Director shall sign and issue all Certificates of Approval for the installation, repair or alteration of all air conditioning and/or refrigeration work. Said certificate shall not be issued until all work has been inspected by him and found to comply with all the requirements of this Code. Said certificate shall contain mechanical data, name of the owner or owners, and exact location of the building or premises where the installed work was accomplished. The Mechanical Inspection Division shall keep a record of the equipment inspected in each building giving the description of the equipment, the name of the owner or owners of the building, the inspection date and the amount collected for such inspections and the name of the installer for whom the inspection was made.
SECTION 108 - POSTING OF ANNUAL CERTIFICATE OF APPROVAL.
The owner shall post the issued Certificate of Approval in the machinery room within 10 feet of the pressure imposing element. The Director shall maintain a file and record of the Certificates of Approval issued at each location.
108.1 - Instructions. Every owner of every Class A, B or C system shall conspicuously post, as near as practical to the unit, the amount of refrigerant charge, kind of refrigerant, operating directions, and precautions to be observed in case of a breakdown or leak, including the following:
1. Instructions for shutting down the system in case of an emergency.
2. The name, address and day and night telephone numbers for obtaining service.
3. The name, address and telephone number of the municipal inspection department having jurisdiction and instruction to notify said department immediately in case of emergency.
4. A sign showing location of main plant switch.
5. The name or license number of Operating Engineer in charge.
6. Location of nearest fire alarm box.
7. Instructions for letting out refrigerant in case of fire.
SECTION 109 - AIR CONDITIONING AND REFRIGERATION CONTRACTOR CERTIFICATION
109.1 - License Required. A person, firm or corporation engaging in the business of installing, constructing, reconstructing, altering, repairing, or servicing any air conditioning or refrigeration system or apparatus or parts thereof, (excluding plug-in types), and who does not hold, or does not employ a person who holds, a Class "A" Air Conditioning and Refrigeration contractor's is in violation of this code.
A Class "A" Air Conditioning and Refrigeration Contractor license issued under this chapter shall not be required for the following allied contractors who are performing only their trade work on a system or apparatus having air conditioning or refrigeration work regulated by this code:
1. Electrical
2. Plumbing
3. Gasfitting
4. Sheet-metal
5. Insulating
All of the above must, however, perform their trade work in association with or in support of an air conditioning or refrigeration system.
6. Stationary Engineers certified in accordance with this Code, may perform work on the air conditioning and refrigeration systems, apparatus or parts thereof to include installation, construction, alteration, reconstruction, repair or service. This work is allowed only within the building, mechanical plant or plants, in which the certified Stationary Engineer is hired to operate, provided however, the necessary Mechanical Inspection Division permits required by this Code have first been obtained. A Stationary Engineer applying for a permit with the Mechanical Inspection Division for the above work at his building, mechanical plant in which he is hired to operate shall provide his Boiler, Air Conditioning or Refrigeration License number. His license must be current and the status must be "Active".
SECTION 110 - APPLICATIONS FOR EXAMINATIONS
Examination applicants for the Class "A" Air Conditioning and Refrigeration Contractor License or the Class "B" Journeyman Mechanic License shall complete and submit the application to the nationally recognized testing company approved by the City of New Orleans. The application forms shall be furnished by them and they shall be properly completed in accordance with their information brochure. All applications for examination shall be submitted to the recognized testing company under contract with the City of New Orleans, prior to the deadline dates published in their issued information brochure. The application shall be accompanied by the appropriate examination fee.
SECTION 111 - EXAMINATIONS
Applicants for examinations shall meet the following requirements:
1. Applicants must be at least eighteen (18) years of age.
2. An applicant for a Contractor license must furnish satisfactory proof of having at least five (5) years experience in the field of installation and repair of air conditioning or refrigeration systems. Satisfactory completion of a Mechanical Engineering Curriculum or Registration as a Professional Engineer shall constitute satisfactory completion of this requirement.
3. An applicant for a Contractor license must have someone in attendance in order to receive communications from the Mechanical Inspection Division of the Department of Safety and Permits, or other persons concerned, during business hours.
4. An applicant for a Contractor's License must show successful completion and graduation in a course of study in air conditioning and refrigeration systems offered by a trade school or technical college of recognized standing having at least a two year curriculum. This shall account for four years experience.
5. A Class "A" Air Conditioning and Refrigeration Contractor license may be assigned to only one firm, corporation or business at any time.
6. An applicant for a Class "B" Journeyman Mechanic license must furnish satisfactory proof of having at least four (4) years experience working in the field of installation and repair of air conditioning or refrigeration trade or show successful completion and graduation from an HVAC program at a state accredited trade school or college having at least a two-year standardized associate degree curriculum in air conditioning and refrigeration. Applicants who have completed said HVAC program shall be allowed to test.
7. Each applicant that has passed the examination shall furnish the Mechanical Inspection Division two bust pictures (passport type), 1 inch by 1½ inches in size. Requirement #7 shall not be required if application is made in person.
8. License Issue - Mechanical Inspection Division shall issue the appropriate license. Licenses issued in accordance with the provisions of this code shall not be assignable or transferable to any other person.
Each license issued shall identify the name and address of the person to whom the license is issued, the date issued and the expiration date. Before any license is issued under this code the applicant must pay the fee required for such license as defined in this code.
SECTION 112 - EXAMINATIONS
112.1. - Examinations shall be held on dates as identified in the issued Candidate Information Brochure of the nationally recognized testing company under contract with the City of New Orleans.
112.2 - When a candidate passes the examination the appropriate license must be issued within 1 year. The license must be signed by the Director.
The license holder must have his license in his immediate possession at all times while performing the work for which he is licensed and shall display it upon demand.
All licenses shall be issued by the Mechanical Inspection Division.
112.3 - Re-examinations. If an applicant fails to make a passing grade on the examination, he is permitted to apply to be re-examined at the next regularly scheduled examination date. There is no limit to the number of examinations a candidate is allowed to take.
112.4 - Definition Of License Classifications.
Class "A" Air Conditioning and Refrigeration Contractor. Any person, firm or corporation engaging in the business of installing or contracting to install or repairing or contracting to repair air conditioning, refrigeration or any mechanical equipment associated with the refrigeration process.
Class "B" Journeyman Mechanic. Any person engaged in the trade of installing or repairing air conditioning and/or refrigeration equipment, materials or apparatus. A Class "B" Journeyman Mechanic must be employed by and work under the supervision of a Class "A" Air Conditioning and Refrigeration Contractor.
112.5 - License Revocation Or Suspension. Licenses issued under this code may be revoked or suspended for reasons defined in this code. However, the Director may find that the public health, safety & welfare will be adequately protected by a warning or a suspension for a definite period of time not to exceed two years. Upon such finding the Director shall issue such warning or order such suspension. Upon revocation, the Mechanical Inspection Division shall not accept an application for a new license or a renewal within two (2) years from the date of such revocation unless a shorter time period is granted at the discretion of the Director based on the circumstances of the revocation or suspension.
If an Air Conditioning and Refrigeration Contractor license is suspended or revoked, a new license shall be issued to such person only after application as a new applicant, and passing the required examination.
112.6 - Revocation Or Suspension Reasons.
1. Interfering, impeding, or obstructing the legal operation of, or intentionally damaging, any item governed by this Code. In addition, threatening, abusing, insulting, interfering with, impeding or obstructing any individuals in connection with the operations or inspections of any equipment regulated by this code, or the administration of this Code.
2. Violating, either willfully or maliciously, or by reason of incompetence, any provision of this code.
3. Conviction of any offense involving the defrauding of any person for whom a service has been rendered or contracted to be rendered under this chapter.
4. Fraud or misrepresentation in obtaining a license or permit.
5. Conviction of drunkenness or the use of narcotics.
6. Adjudication of insanity.
7. Securing a permit for mechanical work not actually performed by the Class "A" Air Conditioning and Refrigeration Contractor or by certified employees under his control, supervision, direction and responsibility.
8. Securing a permit under any pretext for an installation concerning which the applicant has no valid contract.
9. Performing any air conditioning or refrigeration work as defined herein for which no mechanical permit has been obtained.
10. Refusing to finish work for which a permit was taken and for which payment was accepted.
11. False, misleading or deceptive advertising.
12. Any medical reason wherein a physician's medical opinion is provided to the Director indicating the person certified is unable to satisfactorily perform the duties and functions expected of a Class "A" Air Conditioning and Refrigeration, or a Class "B" Journeyman Mechanic license holder, and any further performance in the air conditioning or refrigeration field as a result of present continued activity or any future license renewal would be a danger to himself and endanger the life and property of others.
112.6.1 - License Renewal. The Director may withhold the renewal of any license by the same process used for revocation or suspension of issued licenses, as described in this Code.
112.7 - Code Violation Hearing. If needed, the Director shall initiate a hearing, in conjunction with the Building Official or the Chief Mechanical Inspector to review a code violation the Chief Mechanical Inspector has determined to exist, that would effectuate any license issued by the Mechanical Inspection Division to be suspended or revoked.
112.8 - Notice Of Hearing. Any time the Director is shown the existence of one or more violations that are grounds for revocation, or there is filed with the Mechanical Inspection Division a complaint of any person alleging the existence of any such violations, and if the Director has determined these grounds to be valid, it shall be his duty to serve upon the alleged violator a notice of the alleged grounds for revocation. The notice shall be served upon the holder of the license stating the time, date, and place of a violation hearing. The written notice shall be served not less than 15 days prior to the hearing. The notice shall enumerate the cause or causes for suspending or revoking the license. The notice may be mailed by regular and registered or certified mail to the holder of the license at the address of his place of business as given by him on his application for the license, or it may be served on him in person by a Police Officer or employee the Mechanical Inspection Division of the Department of Safety and Permits. The alleged violator shall have the right to appear at such hearing, be represented by counsel, produce evidence, and cross-examine witnesses. If after such hearing, it is determined that one or more of the above grounds do exist for suspension or revocation, the Chief Mechanical Inspectors final action shall be coordinated with the Building Official or the Director. The Chief Mechanical Inspector shall enter a written finding to the Director of the Department of Safety and Permits.
112.9 - Legal Advisor. The City Attorney shall be legal advisor to the Director.
112.10 - Appeal Procedure. An appeal from this decision may be taken to the Board of Building Standards and Appeals within ten (10) days of written notification to the appellant.
SECTION 113 - INSURANCE
Before a Class "A" Air Conditioning and Refrigeration Contractor license is issued (initial) or re-issued (renewal), each certified Class "A" Air Conditioning and Refrigeration Contractor must provide evidence of the following to the Director when he registers with the Mechanical Inspection Division.
113.1 - Minimum Insurance Requirements.
1. Workers' Compensation Insurance in accordance with Louisiana state law.
2. Comprehensive general liability insurance coverage with limits of not less than $500,000 per occurrence for bodily injury and $250,000 per occurrence for property damage, with coverage extended as follows:
a. Operations-premises liability;
b. Independent contractor's liability-broad form;
c. Contractual liability - broad form;
d. Completed operations and products liability.
All such insurance shall be issued by a company duly registered and/or authorized to write such insurance in the State of Louisiana. Compliance with this section shall be considered as having been met when a copy of the policy or a certificate of insurance has been filed with and approved by the Department of Safety and Permits. Such policy shall include an endorsement thereon that the Department of Safety and Permits will be notified at least 10 days in advance in the event the policy or policies are canceled or permitted to lapse by not renewing before the expiration date of the certificate.
SECTION 114 - FEDERAL IDENTIFICATION NUMBER AND OCCUPATIONAL LICENSE
Before a Class "A" Air Conditioning and Refrigeration Contractor license is issued (initial) or re-issued (renewal), each certified Class "A" Air Conditioning and Refrigeration Contractor must provide his Federal Identification (ID) number and his City of New Orleans Occupational License Number or Certificate of Registration Number to the Director when he registers with the Mechanical Inspection Division.
SECTION 115 - LICENSE FEES
(A) To register a license an applicant shall pay the applicable fee as follows:
1. Class "A" Air Conditioning and Refrigeration Contractor .....$125.00
2. Class "A" Air Conditioning and Refrigeration Contractor (Inactive) .....$30.00
3. Class "B" Journeyman Mechanic .....$60.00
(B) Fees for license registration shall be remitted to the Mechanical Inspection Division and made payable to the "City of New Orleans."
115.1 - Payment Of Fees: Dates For Renewal Of Active Licenses. The registration fee shall be paid at the time the application is presented for the initial or renewal license issuance.
The Class "A" Air Conditioning and Refrigeration Contractor License shall expire on the applicant's date of birth. The renewal registration fee for the Class "A" Air Conditioning and Refrigeration Contractor is due and payable to the "City of New Orleans" on the first regular day of business after the applicant's date of birth. No license renewal shall be issued unless all work specified on permit(s) filed more than three months prior to the applicant's date of birth has been completed, or a written reason, sufficient to the Director, has been submitted and approved, indicating why the job installation(s) remains incomplete.
A single license shall be issued to any contractor applicant successfully satisfying all of the requirements of the City for both of the trades of Class "A" Master Gasfitter and Class "A" Air Conditioning and Refrigeration Contractor. His issued license shall be known as the "Dual Contractor License". The "Dual Contractor License" shall also expire on the applicant's date of birth. Application and renewal fees for the "Dual Contractor License" shall be submitted to the Director prior to the first regular day of business after the applicant's date of birth.
Application and renewal fees for the Air Conditioning and Refrigeration Contractor license shall be submitted to the Director prior to the applicant's date of birth.
License holders may choose between one-year and two-year renewal periods.
1. The renewal fee for a one-year renewal shall be due annually on the first regular business day after the applicant's date of birth.
2. The renewal fee for a two-year renewal shall be due biennially on the first regular business day after the applicant's date of birth.
Should a Class "A" Air Conditioning and Refrigeration Contractor fail to renew his license prior to the first regular day of business after his date of birth, or fail to complete the work specified on his permit(s) issued more than three (3) months prior to his date of birth, a delinquent fee of $10.00 per month shall be added to the renewal fee beginning on the first regular day of business after his date of birth.
No permit application shall be processed, nor shall any permit be issued to any applicant who has not been issued a current valid license for the year of the permit application.
Failure to renew a Class "B" Journeyman Mechanic license prior to the first regular day of business after his date of birth shall require a delinquent fee of $5.00 per month added to the renewal fee beginning on the first regular day of business after his date of birth.
Failure to renew any Class "A" Air Conditioning and Refrigeration, or Class "B" Journeyman Mechanic expired licenses within a one year period shall require a new application and re-examination and shall be considered as a new applicant.
SECTION 116 - INACTIVE LICENSE
A Class "A" Air Conditioning and Refrigeration Contractor, who so desires may, by written request to and approval of the Director, change his license to an inactive status. The Class "A" Air Conditioning and Refrigeration Contractor may continue his inactive status by paying an annual renewal fee of $25.00. The inactive Air Conditioning and Refrigeration license expires on the applicant's date of birth of the year of issue. The inactive status license must be renewed each year and the Director must be notified in writing that the contractor desires to remain in the inactive status for the ensuing year.
The Class "A" Air Conditioning and Refrigeration Contractor may revert his license back to an active status by a written request to and approval by the Director. Reverting the license back to the active status requires the payment of the full active fee as required in this Code.
No Class "A" Air Conditioning and Refrigeration Contractor shall engage in the business as an air conditioning or refrigeration contractor while his license is in an inactive status. An inactive license holder can, however engage in air conditioning and refrigeration work under the supervision of an active first class license holder.
Only one Air Conditioning and Refrigeration Contractor status change to inactive shall be allowed in any twelve (12) month period.
SECTION 117 - PROHIBITION AGAINST LICENSE TRANSFER
No Class "A" Air Conditioning and Refrigeration Contractor shall assign or in any way convey his license to anyone by power of attorney or any other process or become involved in any type of agreement, assignment or use whereby he will not have supervision, direction, control or responsibility for the air conditioning and/or refrigeration work for which he has obtained a permit from the Mechanical Inspection Division of the Department of Safety and Permits.
No Class "B" Journeyman Mechanic shall assign or in any way convey the use of his license, or any rights thereunder, to anyone by power of attorney or any other process.
SECTION 118 - AIR CONDITIONING AND REFRIGERATION CONTRACTORS' AND OWNER'S RESPONSIBILITIES
118.1 - The Class "A" Air Conditioning and Refrigeration license holder shall keep on file with the Director, a letter designating which person, partnership, firm or corporation he represents. He shall notify the Director within 10 days of any status change. The Class "A" Air Conditioning and Refrigeration license holder shall represent only one person, partnership, firm, or corporation.
118.2 - Every Class "A" Air Conditioning and Refrigeration Contractor, certified in accordance with these regulations, shall be responsible for any defects of construction installed by him until such time as a Certificate of Approval has been issued by the Director. Also, any and all defects (discrepancies) that may have been concealed by such Class "A" Air Conditioning and Refrigeration Contractor and discovered after a Certificate of Approval has been issued shall be the responsibility of and corrected by said Class "A" Air Conditioning and Refrigeration Contractor.
After the issuance of the Certificate of Approval by the Director, the person, firm or corporation in whose name the utility service is contracted for, shall be responsible for any and all defects.
SECTION 119 - DISPLAY OF AIR CONDITIONING AND REFRIGERATION CONTRACTOR'S SIGN
Every location where the installation of air conditioning and/or refrigeration work or any work of a mechanical nature is being done, shall have displayed in a conspicuous place, a sign giving the name and address of the person, firm or corporation doing the air conditioning and/or refrigeration work. The sign shall include the license number, name, address and telephone number of the person, firm or corporation and the words "CLASS "A" AIR CONDITIONING AND REFRIGERATION CONTRACTOR" in letters not less than two (2) inches high. Failure to display such sign by the installing Class "A" Air Conditioning and Refrigeration contractor or the display of such a sign by other than duly certified Class "A" Air Conditioning and Refrigeration Contractors shall constitute an attempt to circumvent the safety and welfare of the general public and shall be in violation of this Code.
119.1 - Every Class "A" Air Conditioning and Refrigeration Contractor shall permanently install a sign on each work vehicle utilized in the performance of his duties and responsibilities as a Class "A" Air Conditioning and Refrigeration Contractor as defined in this Code. The vehicle sign shall contain the license number of the Class "A" Air Conditioning and Refrigeration Contractor, the name, address and the telephone number of the person, firm or corporation, in letters not less than two (2) inches high.
119.2 - Public Advertising Or Advertisement Of Services.
1. Every Class "A" Air Conditioning and Refrigeration Contractor advertising or proposing to advertise to the general public for the purposes of obtaining any of the types of air conditioning and/or refrigeration work, in Orleans Parish, as defined in this Code, shall provide his license number, the name, address and telephone number of the person, firm or corporation.
2. Advertising for the purposes of obtaining work in Orleans Parish as defined in this Code, by any person other than a certified Class "A" Air Conditioning and Refrigeration Contractor shall constitute an attempt to circumvent the general health, welfare and safety of the public and shall constitute a violation of this Code.
3. The display of such a sign or advertising for the purposes of obtaining work by any person other than a duly certified Class "A" Master Gasfitter Contractor shall constitute a violation of this Code.
4. Deceptive or false advertising shall constitute an attempt to circumvent the general health, welfare and safety of the public and shall constitute a violation of this Code.
SECTION 120 - BOILERS, HEATING SYSTEMS AND UNFIRED PRESSURE VESSELS
120.1 - All power boilers and low pressure heating boilers shall be inspected annually.
EXCEPTIONS:
1. This Section shall not apply to boilers, heating systems or unfired pressure vessels in marine or railroad service, which is under the inspection regulations of the United States Government.
2. This Section shall not apply to low-pressure boilers, low-pressure hot water or steam heating systems and hot water supply systems located in a private residence or dwelling of two (2) families or less.
3. This Section shall not apply to any unfired pressure vessel of 35 gallons capacity or less or any vessel designed for pressures not exceeding 250 psi provided they comply with the rules for construction and installation in this Code and are stamped as required by ASME B31.9.
120.2 - All unfired pressure vessels over 35 gallons shall be inspected at least once annually.
120.3. All boilers, heating systems or unfired pressure vessels shall be inspected by the Director during their installation.
120.4 - The owner or user shall apply a hydrostatic test to a boiler, heating system or unfired pressure vessel when advised to do so by the Director.
SECTION 121 - ANNUAL OPERATING CERTIFICATE FEES AND PERMITS
121.1 - The following fees shall be charged annually:
Boilers thru 20 HP .....$20.00
Boilers 21 HP thru 100 HP .....$25.00
Boilers over 100 HP .....$30.00
Unfired Pressure Vessels which cannot be inspected internally .....$15.00
Unfired Pressure Vessels which can be inspected internally .....$20.00
121.2 - Every person, firm or corporation proposing to install or repair boilers, heating systems, hot water supply systems or unfired pressure vessels shall file a written request for a permit with the Director and pay the following fees:
Boilers - 1 thru 10 HP .....$25.00
Each additional HP .....$3.00
Unfired Pressure Vessels not designed for internal inspections .....$20.00
Unfired Pressure Vessels designed for internal inspections thru 200 gallons nominal fluid capacity .....$25.00
Over 200 gallons, each additional 100 gallon capacity .....$35.00
Repairs for the first $1,500.00 of cost .....$35.00
Each $1,000.00 over the first $1,500.00 or part thereof .....$10.00
Permits obtained after installation has begun shall pay the regular fee plus a penalty fee of five (5) times the regular fee amount.
SECTION 122 - REVOCATION OF CERTIFICATES
When a boiler, heating system or unfired pressure vessel is found to be in a dangerous condition and its continued operation would be a source of danger to life and property, the Director shall immediately revoke the Certificate of Approval and the owner or user shall be ordered to cease operating same immediately. If the owner or user refuses to comply with the order, the Director shall have the authority to order the Utility Company to disconnect the service from the building, premises or structure where the dangerous boiler, heating system or unfired pressure vessel is being operated.
SECTION 123 - SPECIAL EVENTS AIR CONDITIONING AND REFRIGERATION
A Special Event shall include, but not be limited to fairs, festivals, carnivals, circuses, road shows, trade shows, concerts, displays, expositions and/or such other functions with a temporary status generally taking place outdoors and/or indoors at a permanent location or building utilizing the electrical service at that location or building to power the temporary installation of air conditioning and/or refrigeration equipment or other mechanical equipment to support the Special Event. This includes the temporary installation of air conditioning and/or refrigeration equipment or other mechanical equipment of any description to be powered by the use of self-generated electrical equipment either rented or owned by any of the types of Special Event. A permit is required for the Special Event temporary installation air conditioning and/or refrigeration or other mechanical equipment of any description. All Certificates of Approval issued for the Special Events air conditioning and/or refrigeration equipment or mechanical equipment of any description may be revoked at the discretion of the Director if the continued use of such mechanical equipment for the Special Event is deemed unsafe and not in the interest of the safety, health and welfare of the general public for which the event was initially allowed.
SECTION 124 - DISCONTINUANCE OF UTILITY SERVICES
(A) Whenever the Director determines the construction, repair or installation of any air conditioning and/or refrigeration system, or power source, or mechanical equipment at any municipal address or location to be in an unsafe, dangerous, hazardous or perilous condition and imminently threatening to the safety, health and welfare of the users, occupants or the general public, immediate notification shall be given to the utility company to disconnect the meter or remove any utility service to the building or location. No utility service shall be resumed until the necessary corrections have been completed as required by this Code.
(B) Whenever, in the opinion of the Director, any air conditioning and/or refrigeration installation of mechanical equipment or power source in any building or any mechanical construction, installation, or repair work has been installed or is being used in violation of this Code or is being used in violation of the use provisions of the Comprehensive Zoning Ordinance, as interpreted by the Director in his authority pursuant to the City of New Orleans Home Rule Charter, the Director shall send written notice to the person, firm or corporation responsible for the violation(s) to correct such condition(s) within the time specified in the written notice. This period may not be extended except by written permission from the Director.
Failure to comply with this notice shall empower the Director to:
1. File charges in the Municipal Court of the City of New Orleans; and/or
2. Seek relief through Civil District Court or another Court of competent jurisdiction; and/or
3. Notify, as provided in Chapter 6, Article II, of the Code of the City of New Orleans, the owner of record to appear before an Administrative Hearing Officer to show cause why the said owner and/or person should not be adjudicated as a violator.
If the above Courts and/or Administrative Agency determines that the owner and/or person is in violation of the provisions of this Code or the use provisions of the Comprehensive Zoning Ordinance, as interpreted by the Director in his authority pursuant to the City of New Orleans Home Rule Charter, and such violations have not been corrected within the time period stipulated by the judge or hearing officer, the Chief Mechanical and/or Chief Electrical Inspector shall have authority to order the service of the utility company to be discontinued until such time the violations have been corrected. When the violations have been corrected and the location is re-inspected by the Director, he shall notify the utility company in writing that the utility service(s) may be reconnected. Corrections of all such violations must be performed by licensed contractors.
(C) If any premises or location has been without gas service or electrical power for a period exceeding six (6) months, a permit must be obtained and a re-inspection made prior to the connection of any utility service.
SECTION 125 - WORK BY OTHER THAN MECHANICAL CONTRACTORS
No person, firm or corporation, erecting, repairing, or altering buildings, erecting signs, altering, changing or installing plumbing or engaged in any other work, shall close in or conceal any wiring or raceway, nor cut, break, destroy, disconnect or in any other manner interfere with the arrangements of any air conditioning and/or refrigeration equipment whether inside or outside of any building or premises without receiving a permit from the Director. Before such permit will be issued, said person, firm or corporation shall provide the Director with a written notice at least forty-eight (48) hours before such contemplated work is to commence. The work of altering, changing or disconnecting such air conditioning and/or refrigeration equipment, by other than a mechanical contractor, must be done under the supervision of a Class "A" Air Conditioning and Refrigeration Contractor.
SECTION 126 - EXTRA INSPECTIONS FEES
(A) Extra Inspection or wasted trip - When any person, firm or corporation, after notice has been given to the Director, shall be found to have violated any of the requirements of this Code, or when through any such violation by any person, firm or corporation doing the work, it shall become necessary to make extra inspections because of a wasted trip, a fee of $75.00 shall be charged.
This charge is for each and any extra inspection made necessary as a result of blatantly incomplete work, inaccessibility to perform the inspection or for alterations to work previously accepted. This fee is in addition to any regular required permit fees.
(B) Fire Marshal Inspection - When any person, firm or corporation requests a complete mechanical inspection of existing installations as ordered by and/or in compliance with the Louisiana State Fire Marshal Act, a fee of $25.00 shall be charged.
(C) After Hour Inspections - When any person, firm or corporation requests a mechanical inspection of any installed mechanical equipment to be performed at a time other than the regular designated working hours of the Mechanical Equipment Inspectors of the Department of Safety and Permits, the request and reason for the after hour inspection must be made to and approved by the Director prior to any inspector assignment. A fee of $175.00 shall be charged to the person, firm or corporation requesting this after-hour inspection. Payment of this fee must be made to the "City of New Orleans" within forty-eight (48) hours of the request for the inspection and is to be paid in addition to any regular required permit fees in this Code.
SECTION 127 - EXEMPTIONS
Nothing in this Code shall apply to companies regulated by the Louisiana Public Service Commission or the utility company where mechanical work is performed on the utility company property or on the supply side of any utility company meter.
SECTION 128 - BASIC STANDARDS
No air conditioning and/or refrigeration work shall be installed or placed in or on any building, structure or premises, unless this work is in conformity with approved methods of construction. Compliance with the regulations in the applicable safety codes shall be "prima facie" evidence of conformity with such approved methods.
All mechanical devices, fittings, materials, equipment, and appliances shall be those approved for the purpose for which they are used. Only such mechanical devices, fittings, materials, equipment, and appliances, that are constructed in conformity with their listing or labeled by a testing laboratory acceptable to the Director, shall be installed. The satisfactory listing or labeling of these devices, fittings, materials, equipment, and appliances shall be the "prima facie" evidence of conformity with the requirements of this Code.
128.1 - General - Storage Rooms And Mechanical Rooms. All Storage Rooms, Mechanical Rooms, Boiler Rooms, and other rooms containing electrical and/or mechanical equipment shall comply with Section 315 of the International Fire Code, as adopted by the City of New Orleans. Rooms shall not be used for general storage and shall be free and clear of all obstructions that may prevent access and maintenance.
SECTION 129 - STANDARD AIR CONDITIONING AND REFRIGERATION MATERIALS
Before any air conditioning and refrigeration material, appliance, or equipment is used, it shall be constructed in conformity with the current methods (to include, but not be limited to: Underwriters Laboratories, Inc. (UL), Factory Mutual (FM), Canadian Standards Association (CSA),American Gas Association (AGA) and others listed by the SBCCI Public Safety Testing & Evaluation Service, Inc. (PST & ESI) to insure safety to life and property.
SECTION 130 - ALTERNATIVE MATERIALS, METHODS AND EQUIPMENT
The provisions of this Code are not intended to prevent the installation or use of any material or to prohibit any method of construction not specifically prescribed by this Code, provided any such alternative has been approved by the Director. The Director shall approve any such alternative, provided he finds that the alternative for the purpose intended is at least the equivalent of that prescribed in this Code in quality, strength, effectiveness, fire resistance, durability and safety. The Director shall require that sufficient evidence or proof be submitted to substantiate any claim made regarding the alternative. The Director may recommend an amendment to this Code in order to make permissible the use of said alternate. If in the opinion of the Director, the evidence and proof are not sufficient to justify approval or recommendation for an amendment, the applicant may refer the entire matter to the Board of Building Standards and Appeals as specified in Article 112 of the New Orleans Amendments to the International Building Code, as amended.
SECTION 131 - TESTS OF MATERIALS AND SYSTEMS OF CONSTRUCTION
Where new and/or alternative systems of construction, qualities of materials or tests are proposed for use, tests may be required by the Director. Such tests shall be made at the expense of the owner or his agent by a testing laboratory or other organization approved by the Director. When required by the Director, such tests shall be witnessed by him or his designee. The owner or his agent shall notify the Director of the time and location of all such tests so that he may be present. Certified copies of all test reports shall be filed with the Director for his final approval before the systems of construction or materials are used.
SECTION 132 - ELEVATORS, MOVING STAIRS AND DUMBWAITERS
132.1. - Each elevator, dumbwaiter, hoist, moving stair and chair lift, used or proposed to be used in this City, shall be inspected by the Director; if found to be suitable and to conform to the requirements of this Code, the Director shall issue the owner or user thereof, an inspection certificate. Such inspection certificate shall be valid for twelve (12) months from its date of issuance and shall be posted in a conspicuous place.
132.2 - The Director may at any time suspend an inspection certificate when, in his opinion, the elevator, moving stairs, dumbwaiter or hoist for which it was issued may not continue to be operated without danger to the public safety. Such suspension of an inspection certificate shall continue in effect until said elevator, moving stairs, dumbwaiter or hoist shall have been made to conform to the requirements of this Code.
132.3 - Not more than twelve (12) months shall lapse between inspections of elevators, moving stairs, dumbwaiters, hoists and other installations as listed in ANSI A17.1. Interval inspections as prescribed by ANSI A17.1 shall be "prima facie" evidence of compliance with this article.
SECTION 133 - FEES FOR ANNUAL OPERATING CERTIFICATES
For each elevator, moving stairs, dumbwaiter, hoist .....$55.00
133.1 - Every person, firm or corporation proposing to install or repair elevators, moving stairs dumbwaiters, or hoists shall file a written request for an installation permit with the Director and pay the following fees:
For each elevator, moving stairs, dumbwaiter, or manlift (2 thru 10 floors) .....$65.00
For each elevator, moving stairs, dumbwaiter, or manlift (over 10 floors) .....$110.00
For each Workman's Hoist (passenger) .....$270.00
For each Builders Hoist .....$220.00
133.2 - The repair fees for elevators, moving stairs, or dumbwaiter shall be in accordance with this Code.
133.3 - Permits obtained after the installation has begun shall be the listed permit fee plus a penalty fee of five (5) times the listed fee for such work.
SECTION 134 - INSPECTION BY LICENSED INSURANCE COMPANIES
134.1 - Commissioned Inspectors. All inspections required on insured boilers, unfired pressure vessels, refrigeration and/or air conditioning systems and water heaters may be conducted by licensed insurance company inspectors, subject, however, to certain conditions hereinafter set forth. The burden of proving that these conditions have been fulfilled is incumbent on the licensed insurance company.
Any insurance company licensed by the State of Louisiana to inspect and insure boilers, unfired pressure vessels, refrigeration and/or air conditioning systems and water heaters may make application to the Director to have inspectors employed by said insurance companies commissioned as Special Inspectors of the City of New Orleans. Such inspectors shall receive no salary or remuneration of any kind from, nor shall any of their expenses be paid by the City of New Orleans.
The duration of the commissioned Special Inspector shall be conditioned upon his continued employment with the licensed insurance company making the original application, and upon said insurance company's maintenance of the standards required of this Code. The Special Inspector Commission is issued for only one licensed insurance company. The Special Inspector shall notify the Director of any change in status of his employment within 10 days of the change.
All applicants for a Special Inspector's Commission to inspect boilers, unfired pressure vessels, refrigeration and/or air conditioning systems and water heaters shall hold a Boiler and Pressure Vessel Inspector Commission issued by the National Board of Boiler and Pressure Vessel Inspectors.
Any licensed insurance company desiring to qualify an inspector under the provisions of this Article must maintain a regular inspection service in the City of New Orleans and must have at least one duly commissioned Special Inspector.
Every licensed insurance company employing these Special Inspectors shall furnish the Director an inspection report of all mechanical equipment insured and inspected by them, the location of the equipment, the owner or user of the equipment and the date the present inspection certificate on the equipment expires. The report list shall include any added or deleted equipment from the submitted report of the previous year.
Inspections of all boilers, heating systems, unfired pressure vessels, air conditioning and/or refrigeration systems and water heaters, when such objects are insured and inspected as required by this Code. Equipment inspected by an inspector employed by a licensed insurance company and commissioned by the Director as a Special Inspector, will be accepted. This equipment will be exempted from City inspections upon the payment of applicable inspection fees. The inspection of the initial installation of the above objects shall be made by the Director and the inspection fees shall be paid to the City by the owner or user as required. The inspection of all replacement installations which requires the Director's approval of plans and specifications shall also be made by the Director and the applicable inspection fees shall be paid to the City by the owner or user.
134.2 - Fees. For Commercial and Industrial installations, the licensed insurance company shall collect for the City of New Orleans a $10.00 annual certificate fee for each insured boiler, unfired pressure vessel, refrigeration and/or air conditioning system or other insured equipment and a $5.00 annual certificate fee for each water heater.
The fee shall be paid by the owner or user of such insured equipment. These fees shall be made payable to "The City of New Orleans" and submitted to the Mechanical Inspection Division at the time the annual data inspection report is filed with the Director. On all refrigeration and/or air conditioning systems, no exemption from City inspections shall be granted or recognized unless the complete and entire system, exclusive of the prime mover, is insured and inspected.
Special Inspectors shall make all inspections as required by this Code. The inspection reports furnished to the Director shall be on appropriate ASME or National Board of Boiler and Pressure Vessel Inspectors forms or any other form prescribed by the City of New Orleans.
If an inspection report indicates that violations of this Code exist, the licensed insurance company shall cause those violations to be corrected. If said violations are not corrected within thirty (30) days, the licensed insurance company shall report the violation to the Director and he shall cause those violations to be corrected and shall collect from the owner or user the City inspection fee as prescribed within this Code.
If the licensed insurance company fails to inspect and file with the Director a complete report of inspection of the insured boiler, heating system, unfired pressure vessel, mechanical amusement device, air conditioning and/or refrigeration system and water heater within a thirty (30) day period after the expiration date of the last issued certificate on the described objects, an inspection of the described objects shall be made by City inspectors and City inspection fees, as prescribed in this Code shall be collected from the owner or user.
The licensed insurance company shall notify the Director immediately whenever an inspection indicates an unsafe, dangerous or hazardous condition.
The licensed insurance company shall also notify the Director within thirty (30) days on an appropriate ASME or National Board of Boiler and Pressure Vessel Inspector form or form prescribed by the City of New Orleans of all new insurance and discontinuance in insurance on boilers, heating systems, unfired pressure vessels, refrigeration and/or air conditioning systems, and water heaters. If said companies or inspectors fail to comply with the above conditions and requirements, the Director may suspend or revoke commission inspection privileges granted hereunder.
SECTION 135 - STATIONARY ENGINEER
It is unlawful for a person, owner, occupant, firm, partnership, association, or corporation having control or management of any building, structure or plant, to operate or permit to be operated any boiler, steam engine, internal combustion engine, refrigeration and/or air conditioning equipment, in the City of New Orleans without a properly qualified person having the necessary license on the premises at all times while such stationary equipment is in operation.
The exact location of the building, structure or plant shall be indicated on the face of the issued license and this issued license shall be limited to that indicated location only.
Upon failure to comply with the above, thereby creating an unsafe and dangerous condition for the general public, the Director, shall notify the owner in writing to correct such condition within 10 days. This period may not be extended except by written permission from the Director of the Department of Safety and Permits. Upon failure to comply with this notice, the respective Electrical and/or Mechanical Division Chiefs shall request the Utility Company to discontinue either the electric and/or gas service, until such time that a person with a valid license is operating the stationary equipment in the discrepant building, structure or plant. If the utilities have been discontinued, and license compliance has been completed, either the Chief Electrical Inspector or the Chief Mechanical Inspector, or both, shall notify the Utility Company that electric and/or gas service may be restored. (See Sections 153 and 154 of this code for exemptions to these requirements)
SECTION 136 - DEFINITIONS AND REFERENCES
The air conditioning and refrigeration tonnage referred to in this Code shall be in accordance with the most current edition of ASHRAE Standard 15. See Section 104.7 for additional definitions.
SECTION 137 - EQUIPMENT AND SYSTEMS REQUIRING STATIONARY ENGINEERS AND CLASSIFICATION OF LICENSES
137.1 - A First Class License is required for an operator to operate the following:
1. Boilers - unlimited.
2. Steam engines - unlimited.
3. Internal combustion engines - unlimited.
4. Refrigeration and/or air conditioning systems using Group A1, B2 Refrigerants - unlimited.
A Second Class License shall be required for any operator to oversee or manage any of the above equipment under the direct supervision and guidance of a First Class Engineer. The First Class Engineer must be continuously available to advise the Second Class Engineer(s) whom he supervises.
137.2 - A Second Class License is required for an operator to operate the following:
1. Boilers up to 150 horsepower.
2. Steam engines up to 150 horsepower.
3. Internal combustion engines up to 150 horsepower.
4. Refrigeration and/or air conditioning systems using Group A1, B2 Refrigerants; up to 200 tons, but not more than 15 systems.
5. Air Conditioning systems using Group A1 Refrigerants; up to 200 tons but not more than 15 systems, maximum size of any individual unit 60 tons.
A Third Class License shall be required for any operator to oversee or manage any of the above equipment under the direct supervision and guidance of a Second Class Engineer.
The Second Class Engineer must be continuously available to advise the Third Class Engineer(s) whom he supervises.
137.3 - A Third Class License is required for an operator to operate the following:
1. Boilers up to 75 horsepower.
2. Steam engines up to 75 horsepower.
3. Internal combustion engines up to 75 horsepower.
4. Refrigeration and/or air conditioning systems using Group A1, B2 Refrigerants, up to 100 tons.
SECTION 138 - ANNUAL LICENSE REGISTRATION FEES
138.1 - Stationary Engineers License. Every applicant for a license, either upon the original application or for a renewal thereof, shall be required to pay the following registration fees:
First Class Operating Engineer's License
1. Active status .....$55.00
2. Duplicate issue .....$55.00
3. Inactive status .....$25.00
Second Class Operating Engineer's License
1. Active status .....$40.00
2. Duplicate issue .....$40.00
Third Class Operating Engineer's License
1. Active status .....$35.00
2. Duplicate issue .....$35.00
138.3 - Examination Registration. Every examination application for an Operating (Stationary) Engineer or Hoisting and Portable Engineer shall be made on forms furnished by the nationally recognized testing company under contract with the City of New Orleans. Examination fees shall be charged for each examination and must be paid in advance of the examination to the nationally recognized testing company under contract with the City of New Orleans.
The minimum passing grade for a stationary engineer or a hoisting and portable engineer is 70 percent. The examinations are identified in the issued brochure and administered by the nationally recognized testing company under contract with the City of New Orleans.
If an applicant fails to make a passing grade on the examination, he is permitted to apply to be re-examined at the next regularly scheduled examination date. There is no limit to the number of examinations a candidate is allowed to take.
SECTION 139 - ACCEPTANCE OF OTHER TESTING AGENCY CERTIFICATION
139.1 - Any Stationary Engineer that has passed the examination of and received certification by The National Institute for the Uniform Licensing of Power Engineers, Inc. (NIULPE), for any of the levels of classifications listed in Section 137 will be acknowledged and recognized by the Mechanical Inspection Division of the Department of Safety and Permits in lieu of the requirement of an additional examination by the nationally recognized testing agency under contract with the City of New Orleans. The applicant must provide documented evidence of his declared education or training for approval. The level of category and classification shall be determined by the Director. If approved, the Stationary Engineer License will be issued upon presenting the NIULPE certificate, completion of the necessary application forms of the Mechanical Inspection Division and payment of the applicable license registration fee.
139.2 - NCCCO - Testing Agency For Cranes.
SECTION 140 - ACCEPTANCE OF OTHER JURISDICTIONAL CERTIFICATION
The Mechanical Inspection Division of the Department of Safety and Permits will extend to any mechanical contractor, operating engineer or hoisting and portable engineer, that is licensed by another jurisdictional authority, the recognition and acceptance of his certification without the requirement of additional examination provided that the jurisdiction requires passing of an examination given by a nationally recognized testing agency before issuance of license. If approved by the Director, the applicant shall present a copy of his license for the City of New Orleans files and complete the necessary applications as set forth by the Mechanical Inspection Division of the City of New Orleans. The applicant shall pay the appropriate fee for the classification of license for which he is applying. This extended license registration offer does not apply to marine or railroad engineers or any type or classification of engineer not specifically approved by the Director.
SECTION 141 - EXAMINATION FEES
Examination fees are determined by the nationally recognized testing agency under contract with the City of New Orleans.
SECTION 142 - ISSUANCE OF MULTIPLE LICENSES
The Mechanical Inspection Division shall issue a maximum of only one additional or second, license to any successful applicant upon written request to the Director. Payment of an amount equal to the cost of the issuance of the first license shall apply. The issuance of this additional, or second, license shall be available to any First (1st) Class, Second (2nd) Class, or Third (3rd) class stationary engineer (in all classifications) for the purposes of second employment, as long as the second employment is not in conflict with this Code. A "duplicate" license shall be issued only in the event that the applicant is employed at a second location and the exact location of the second employment shall also be indicated on the face of the license.
The issuance of this additional, or second, license shall be affixed with the identical endorsements as the first (original) issued license and the face of the additional, or second, license shall be prominently identified with the word "DUPLICATE". Each additional, or second, license shall expire on the same day as the first (original) issued license. The Director shall not issue any additional or "DUPLICATE" licenses with an inactive status. The "DUPLICATE" license issue is not to be used for split time service by the engineer employed by persons, firms or corporations that own or are in charge of properties at multiple locations. The "DUPLICATE" license does not apply to the Special Operators.
SECTION 143 - RENEWAL OF LICENSE
143.1 - Each license evidencing the necessary satisfactory qualifications of the applicant, according to the classifications stated thereon shall expire on the applicant's birth date, and must be renewed annually in order to permit the holder thereof to engage in the profession, trade or calling of Stationary Engineer or Hoisting and Portable Engineer in the City of New Orleans, according to the classification stated on said license. Each applicant shall furnish, to the Mechanical Inspection Division, two photographs (passport type), 1 in. × 1½ inches in size, at the time of applying for the initial license issuance or for license renewal. The photographs shall have been taken within a three (3) month period prior to the date it is affixed to the issued license.
143.2 - Inactive License. First class engineers not actively pursuing or involved in the practice of their trade as a Stationary Engineer may request, at their next renewal date, that their license be placed in an inactive status. The inactive license status shall apply only to a first class license holder. The fee for the issuance of the inactive license shall be in accordance with this Code. Licenses may be placed on an inactive status only on the date of renewal and only once during any twelve month period. The face of the inactive license shall be affixed with the identical endorsements as the active license and the face of the license shall be prominently identified with the word inactive. The inactive license may be reverted back to the active status at any time; however the full fee for the issuance of an active license will be required, in accordance with this Code. Inactive licenses do not apply to Hoisting and Portable Engineers or Special Operators.
143.2.1 - The first class engineers request to make any status change of his license shall be made in writing to the Director. All license status changes shall be coordinated with and approved by the Director, and become a part of the license holder's history record. The initial issuance of any first class stationary engineer's license shall always be with an active status. The new inactive license shall have the same expiration date as the original active license. No inactive status license shall be approved or issued by the Director for any additional, or second, license issue, in accordance with this Code. There shall be no limit to the number of years a Stationary Engineers license may remain in the inactive status.
143.2.2 - A first class stationary engineer in control of or operating any type of equipment while their current license is inactive will be in violation of this Code.
SECTION 144 - FAILURE TO RENEW LICENSE
License renewal is due on the first regular day of business after the applicant's birth date. Each applicant failing to make a timely application for renewal of his license shall pay a delinquent fee of $5.00 for each month or part thereof that his license is delinquent, to a maximum of two (2) years.
If a Stationary Engineer or Hoisting and Portable engineer's license has expired for a period in excess of two (2) years after their issue date or renewal date, a re-examination is required. Any justifying excuse acceptable to the Director shall be considered to approve the payment of the delinquent fees in lieu of the re-examination requirement.
If a Special Operator license holder has been expired for a period in excess of two (2) years, re-examination is required.
SECTION 145 - QUALIFICATIONS OF APPLICANTS
A citizen in the United States, over the age of 18 years, may apply for an examination as indicated in this code. The applicant, however, must have served the necessary apprenticeship requirements, and must comply with the following qualifications. All applicants must furnish one (1) letter of reference, and one (1) personal request letter. The letter of reference should be from the applicant's present or former employer, attesting to his experience and competence. The personal request letter must be addressed to the Director indicating the classification and desired type of equipment for which he wishes to be examined.
SECTION 146 - EXPERIENCE REQUIREMENTS
146.1 - An applicant for a license as a first-class engineer shall be an operating engineer, with four (4) years of practical experience in the management, operation or construction of steam engines, boilers, internal combustion engines, refrigeration or air conditioning equipment except that those who are graduates of a recognized technical college or a graduate of a U.S. Department of Labor recognized apprenticeship training school, are required to have two (2) years of practical experience.
146.2 - An applicant for a license as a second-class engineer shall be an operating engineer, having at least three (3) years of practical experience in the management, operation or construction of steam engines, boilers, internal combustion engines, refrigeration or air conditioning equipment; except that those applicants who are graduates from a recognized technical college, trade school or a graduate of a U.S. Department of Labor recognized apprenticeship training school, are required to have one and one-half (1½) years of practical experience.
146.3 - An applicant for a license as a third-class engineer shall have at least 2 years experience as an apprentice or junior engineer or fireman, etc., except that graduates of a recognized technical college, trade school or a graduate of a U.S. Department of Labor recognized apprenticeship training school, are required to have one (1) year of practical experience.
146.4 - An applicant for a Special Operator license to operate boilers, steam or internal combustion engines specified in this Code, shall be an operating engineer, having at least 2 years practical experience as an apprentice in the operation of steam engines, boilers, or internal combustion engines. Applicants for a Special Operator licenses coming under the classifications of this Code must, to the satisfaction of the Director, establish their familiarity with the operation of the equipment in their care.
146.5 - An applicant for a license to operate all HOISTING AND PORTABLE equipment as defined in this Code, must have at least two (2) years experience. Applicants for licenses coming under the classifications of this Code must, to the satisfaction of the Director, establish their familiarity with the type of equipment they are to operate. Hoisting and Portable applicants must furnish one (1) letter of reference, and one (1) personal request letter. The letter of reference should be from the applicant's present supervisor verifying the particular type(s) of equipment to be operated. The personal request letter must be addressed to the Director, specifying the particular type(s) of equipment for which the applicant wishes to be examined.
SECTION 147 - VALIDITY OF LICENSES
All licenses as provided for in this Code must bear the signature of the Director in order to be valid.
SECTION 148 - LICENSE SUSPENSION OR REVOCATION
Licenses issued under this code may be revoked or suspended for reasons defined in this code. However, the Director may find that the public interest will be adequately protected by a warning or a suspension for a definite period of time not to exceed two years. Upon such finding the Director shall issue such warning or order such suspension. Upon revocation, the Mechanical Inspection Division shall not accept an application for a new license or a renewal within two (2) years from the date of such revocation, except for medical recovery supported by a physician's report, after The Director's review and approval. A shorter time period may be granted at the discretion of the Director based on the circumstances of the revocation or suspension. If any stationary engineer or hoisting & portable license is suspended or revoked by the Director, a new license shall be issued to such person only after application as a new applicant, and passing the required examination.
148.1 - Revocation Reasons.
1. Violating on more than one occasion, either willfully of maliciously or by reason of incompetence, any provision of this code.
2. Fraud or misrepresentation in obtaining a license.
3. False or deceptive advertising.
4. Conviction of drunkenness or the use of narcotics.
5. Adjudication of Insanity.
6. Any medical reason wherein a physician's medical opinion is provided to the Director indicating that the person certified is unable to satisfactorily perform the duties and functions expected of a Stationary Engineer, Hoisting and Portable Engineer or Special Operator license holder, and that any further performance in the trade would be a danger to himself and/or endanger the life and property of others.
SECTION 149 - NOTICE OF REVOCATION OR SUSPENSION HEARING
Any time the Director is shown the existence of one or more violations that are grounds for revocation, or there is filed with the Mechanical Inspection Division a complaint of any person alleging the existence of any such violations, and if the Director has determined these grounds to be valid, it shall be his duty to serve upon the alleged violator a notice of the alleged grounds for revocation. The notice shall be served upon the holder of the license stating the time, date, and place of a violation hearing.
The notice shall be served not less than 15 days prior to said hearing. The notice shall be sent by the Director and shall enumerate the cause or causes for suspending or revoking the license.
The notice shall enumerate the cause or causes for suspending or revoking the license. The notice may be mailed by registered or certified mail to the holder of the license at the address of his place of business as given by him on his application for the license, or it may be served on him in person by a Police Officer or employee the Mechanical Inspection Division of the Department of Safety and Permits.
All petitions shall be prepared and prosecuted by the Law Department. If proper notice has been served upon the defendant, the hearing may proceed without his presence if he fails to appear. Certified copies of convictions involving cause for suspension or revocation in either the Municipal Courts of New Orleans or in the Criminal District Court of Orleans Parish shall constitute "prima facie" proof of a violation by the license holder.
SECTION 150 - APPEAL PROCEDURE
A decision of the Director may be appealed to the Board of Building Standards and Appeals within ten (10) days of written notification to the appellant.
SECTION 151 - LICENSE VERIFICATION
Any investigations, inquiries or questions regarding the proper certification of the Stationary Engineers at any building location or the Hoisting & Portable Engineers at any construction site shall be directed to the Chief Mechanical Inspector and performed by the duly authorized inspectors of the Department of Safety and Permits.
SECTION 152 - LICENSES DISPLAYED
152.1 - Licenses must be displayed or posted in a conspicuous place in the engine or boiler room or mechanical equipment room, for identification purposes. This license must continuously remain displayed or posted during the tenure of employment of the stationary engineer to whom the license is issued The displayed or posted license shall not be removed after any shift duty or at a time when the stationary engineer to whom the license is issued is not on duty. The "DUPLICATE" license must be issued for any added license display or posting required in accordance with this Code. Copies or reproductions of the issued license by any method or procedure shall be a violation of this code.
152.2 - Engineers who have qualified for a license for the operation of Hoisting and Portable equipment must carry the license on their person while in charge of and/or operating such hoisting and portable equipment as defined in this Code. The issued license must have the Engineers current bust picture (passport type) 1 inch × 1½ inch in size, as a part of the license, for identification purposes.
SECTION 153 - EXEMPTIONS FROM ENGINEER REQUIREMENTS
153.1 - This Code does not apply in any way to engineers:
1. in charge of railroad locomotives of franchised railroads; or
2. employed by a person, firm or corporation operating under Certificate of Public Necessity and Convenience (CPNC); or
3. employed by the United States Government, the State of Louisiana, any of its Boards, Commissions or agencies, or political subdivisions, with the exception of the City of New Orleans; or
4. in charge of steamboats and steamships.
153.2 - Building Safety Summary - Air Conditioning And Cooling. Air conditioning systems using group A1 Refrigerant and/or any open-circuit, water-cooled HVAC systems NOT exceeding a total aggregate size of 300 Tons open may be exempt from the provisions of Section 135 of this Code provided such systems are under automated control by devices that will cause the system to be de-energized from electric power and go to a shutdown condition upon experiencing an equipment malfunction or fault condition and further provided that a Building Safety Summary is submitted and approved, on a case by case basis, by the Director.
The Building Safety Summary shall be prepared by a Registered Louisiana Professional Engineer and shall include as a minimum:
1. emergency procedures in effect in the building; and,
2. a description of the automated HVAC equipment installed in the building; and,
3. a complete description of the operation of the shutdown system under emergency conditions; and
4. Provide details of a Priority Safety Floor Plan consisting of a building floor plan showing the locations of all major mechanical and electrical equipment (i.e. water heaters, boilers, fire pumps, main electrical switchgear and service entrance, domestic and fire water service entrance, etc.) This plan is to be displayed in a prominent location for use by first responders to quickly locate major mechanical and electrical equipment and services. A copy of this Plan shall be located in the main business office.
No Institutional (Group I) facilities or shall be exempt from any provision of this code.
Open-circuit cooling systems shall comply with Section 154 of the Code.
153.3 - Self-contained air conditioning units used for residential, commercial, or industrial purposes having an aggregate of not over 100 tons, using Group A1 Refrigerant, shall be exempt from the provisions of Section 135 of this Code, provided they are protected with the necessary safety devices. Units 5 tons and under shall not be considered in calculating the aggregate tonnage.
153.4 - Equipment Exempted From Stationary Engineer - Boilers. Individual hot water boilers under 200,000 Btu input and operating at a pressure not exceeding 160 psi and temperatures not exceeding 210 degrees F. shall be exempted from the provisions of this Code, provided they are protected with necessary approved safety devices, are listed and are automatically controlled, and are subject to an annual inspection as per Section 106 of this code. Said inspections shall be made by Mechanical Inspectors of the Department of Safety and Permits or Commissioned Inspectors of an authorized insurance company commissioned by the Director of the City of New Orleans, in accordance with the New Orleans Amendments to the International Mechanical Code.
153.5 - Provisions For Exclusion From Full Time Stationary Engineer. Any building, structure or plant with Hot Water Boilers (as defined in Section 104.7 of this Code) exceeding the provisions of Section 153.5 may be exempt from the Stationary Engineer requirements of Section 135 of this code on a case by case basis determined by the Director and provided a licensed 1 st Class Stationary Engineer is present at the premises for a minimum of one (1), seven (7) hour shift per day while such building is regularly open for business. A Stationary Engineer must be available on-call, while not on the premises. In addition, equipment and safety procedures shall be as per Sections 153.5.1 thru 153.5.3 of this code.
153.5.1 - Limitations For Stationary Engineer Exemption - Boilers.
1. Hot Water Boilers stamped A.S.M.E. 'H', with a maximum pressure not exceeding 160psi and a maximum temperature not exceeding 240 degrees F. and a maximum input not exceeding 1,500,000 Btus.
2. Hot Water Heaters stamped A.S.M.E. 'HLW' or ANSI Z 21 with a maximum pressure not exceeding 160psi and maximum temperature not exceeding 210 degrees F. and a maximum input not exceeding 1,500,000 Btus and individual storage capacity not exceeding 250 gallons or an aggregate storage capacity not exceeding of 750 gallons.
3. No building, structure, or plant with Hot Water Boilers exceeding a total aggregate input of 4,500,000 Btus shall be exempt from any provision of this code.
4. No building, structure or plant with Hot Water Boilers fitted with a water column or sight glass or requiring regular blow down shall be exempt from any provisions of this code.
5. No Institutional (Group I) facility shall be exempt from any provisions of this code.
153.5.2 - Building Safety Summary - Boilers. Buildings, structures, or plants may be allowed to comply with Section 153.5 provided a Building Safety Summary is submitted and approved, on a case by case basis, by the Director. A Building Safety Summary shall be prepared by a Registered Louisiana Professional Engineer and shall include as a minimum:
1. Emergency procedures in effect in the building; and
2. Details of automated system to monitor and provide redundancy for the manufactured, installed and code required safety features including discharge pressure and temperature gauges. The automated system shall operate at or below the factor safety set points and de-energize equipment in the event of a system malfunction. Once the equipment has been de-energized, the automation system shall send an alarm to a responsible person; and
3. A signed service agreement with a Licensed Class A Mechanical Contractor registered in the City of New Orleans. This contractor, if necessary, shall be available on a 24-hour basis to respond to and repair the system malfunction; and
4. Provide details of a Priority Safety Floor Plan consisting of a building floor plan showing the locations of all major mechanical and electrical equipment (i.e. water heaters, boilers, fire pumps, main electrical switchgear and service entrance, domestic and fire water service entrance, etc.) This plan is to be displayed in a prominent location for use by first responders to quickly locate major mechanical and electrical equipment and services. A copy of this Plan shall be located in the main business office.
153.5.3 - ADDITIONAL REQUIREMENTS. In addition to the requirements and limitations set forth in 153.5.1 and 153.5.2, the following shall be required of all buildings, structures, plants or equipment in accordance with 153.5:
1. If equipment is de-energized by the automated system, a manual reset will be required to re-energize the equipment. Equipment shall only be re-energized by a licensed Stationary Engineer or Mechanical Contractor with a Class A registration with the City of New Orleans.
2. Maintain and service equipment in accordance with manufacturer's recommendations and in compliance with jurisdictions having authority and maintain for inspections, all maintenance, service and repair records.
3. Perform City and State required annual inspections of the equipment and provide the City Mechanical Inspection Department with copies of the inspection reports. Display State Fire Marshal inspection certificates behind glass in the Boiler Room.
4. Maintain a daily log of equipment temperature and pressure readings and condition of the temperature and pressure relief valves.
5. Actuate pressure relief valves at a minimum interval of six (6) months or in accordance with manufacturer's instructions, whichever is sooner. Maintain logs of pressure relief valve actuation.
6. Provide discharge temperature and pressure gauges for all applicable equipment.
7. Maintain water treatment logs and perform water testing for all applicable equipment.
SECTION 154 - COOLING TOWERS AND WATER COOLED CHILLERS
The owner, occupant, firm, partnership, association or corporation having control of any Building, Structure or Plant operating an open circuit Cooling Tower, Evaporative Condenser or any other aerosol producing equipment shall maintain a 'Water Management Plan' in accordance with ASHRAE Standard 188 - 2015 - Legionellosis: Risk Management for Building Water Systems and ASHRAE 12 - Minimizing the Risk of Legionellosis Associated with Building Water Systems and comply with all relevant sections herein. Equipment shall be maintained, monitored, cleaned and sanitized as defined in the Water Management Plan in accordance with ASHRAE Standard 188 - 2015 and Sections 154.1 thru 154.3
154.1 - Requirements For Water Management Plan. In accordance with ASHRAE 188, the following shall be required of all buildings containing open circuit equipment as per Section 154:
1. Recirculating water to be monitored for pH and biocide levels at least twice per week by the designated responsible person.
2. Equipment shall be drained or partially drained, cleaned of scale, sediment, sludge algae and biofilm and sanitized at least once per year.
3. Disinfectant pretreatment shall be required prior to re-energizing any equipment that has been non-operable, on standby or shut down for any period exceeding 72 hours Water shall be tested by means of bacteria dip slide after equipment restart and in accordance with Requirement #7 of Section 154.1.
4. Maintain for immediate use, an Emergency Decontamination kit, to be used should the presence of Legionella be detected.
5. Records for maintenance, cleaning, sampling, monitoring, sanitizing and any other event having effect on such equipment shall be maintained in a Water Management Log and shall be readily available for inspection by the Director.
6. Equipment shall be inspected and a water sample shall be tested by method of bacteria dip slide at least once per month by a qualified water treatment specialist.
7. A water sample shall be taken by a qualified water treatment specialist at least once every 6 months and shall be tested for Legionella and other bacteria by an independent US Centers for Disease Control and prevention Elite program certified laboratory or any Laboratory approved by the Director and after any of the following occurrences or any other time as determined by the Director. Water samples shall also be tested after any of the following occurrences:
a. any time a bacteria dip slide test indicates levels of bacteria above control points or levels exceeding those stated in table 1 (dip slide)
b. after any power failure or shut down of sufficient duration to allow the growth of bacteria
c. after any loss of biocide treatment sufficient enough to allow the growth of bacteria
8. Water samples are to be taken prior to the addition of any biocide and to be representative of the water condition during normal operation. Results of all water sample testing and equipment inspections shall be recorded in the Water Management Log.
9. The Director shall be notified within 24 hours of any of the above occurrences.
10. Corrective action to be taken for the following bacteriological dip slide indicator results.
154.2 - Corrective Actions For Testing (Dipslide Testing). As per Section 154.2, the following corrective actions shall be taken for the following bacteriological dip slide indicator results:
1. Less than 10,000 CFU/ml: Maintain water chemistry and biocide levels.
2. Equal to or greater than 10,000 CFU/ml AND less than 100,000 CFU/ml: Initiate immediate disinfection by increasing biocide concentration or using a different biocide within 24 hours, review treatment program, retest water within 3-7 days. Subsequent test results must be interpreted in accordance with this Section until level 1 is reached.
3. Equal to or greater than 100,000 CFU/ml and less than 1,000,000 CFU/ml: Initiate immediate disinfection by increasing biocide concentration or using a different biocide within 24 hours, reviewing treatment program, performing visual inspection to evaluate need to perform cleaning and further disinfection. Retest water within 3-7 days. Subsequent test results must be interpreted in accordance with this Section until level 1 is reached.
4. Equal to or greater than 1,000,000 CFU/ml: Initiate immediate disinfection by increasing biocides within 24 hours. Within 48 hours perform remediation of the tower by hyperhalogenating2, cleaning, and flushing. Review treatment program, retest water within 3-7 days. Subsequent test results must be interpreted in accordance with this Section until level 1 is reached.
154.3 - Corrective Actions For Testing (Lab Legionella Testing). As per Section 154.3, the following corrective actions shall be taken for the following Legionella laboratory testing cultures:
1. Less than 10 CFU/ml: Maintain water chemistry and biocide levels.
2. Equal to or greater than 10 CFU/ml and less than 100 CFU/ml: Initiate immediate disinfection by increasing biocide concentration or using a different biocide within 24 hours: review treatment program; and retest water within 3-7 days. Subsequent test results must be interpreted in accordance with this Section until level 1 is reached.
3. Equal to or greater than 100 CFU/ml and less than 1,000 CFU/ml: Initiate immediate disinfection by increasing biocide concentration or using a different biocide (within 24 hours), reviewing treatment program, performing visual inspection to evaluate need to perform cleaning and further disinfection. Retest water within 3-7 days. Subsequent test results must be interpreted in accordance with this Section until level 1 is reached.
4. Equal to or greater than 1,000 CFU/ml: Initiate immediate disinfection by increasing biocides within 24 hours. Within 48 hours perform full remediation of the tower by hyperhalogenating2, draining, cleaning, and flushing. Review treatment program, retest water within 3-7 days. Subsequent test results must be interpreted in accordance with this Section until level 1 is reached. For Legionella results at this level, notify Director within 24 hours of receiving test.
154.4 - Provisions For Exclusion From Full Time Stationary Engineer. Any building, structure or plant operating open-circuit, water-cooled HVAC systems exceeding a total aggregate size of 300 Tons and cooled by use of Open Circuit Cooling Towers or Evaporative Condensers may be exempt from the Stationary Engineer requirements of Section 135 of this code on a case by case basis determined by the Director and provided a licensed 1 st Class Air Conditioning Stationary Engineer is present at the premises for a minimum of one (1), seven (7) hour shift per day while such building is regularly open for business. A Stationary Engineer must be available on-call, while not on the premises. In addition, equipment and safety procedures shall be as per Sections 154.1 thru 154.3 of this code.
Whenever in the opinion of the Director any open circuit Cooling Tower, Evaporative Condenser or any other aerosol producing equipment is in violation of this Code. The Director shall have the authority to order the immediate shutdown of the discrepant equipment and undertake any course of action as defined in section 124 and 137 of this Code. An approved permit shall be required prior to reenergizing any equipment shut down by violation of this code
SECTION 155 - PENALTY TO OWNER: FINES
A person, firm or corporation owning or controlling any steam engine, boiler, internal combustion engine, or any other system coming within the provisions of this Code, who authorizes or permits a person not having a proper and valid license as required under this Code, to take charge of or operate any steam engine, boiler, or any portion of a steam or internal combustion engine, refrigeration and/or air conditioning equipment, and hoisting and portable equipment as defined in this Code, shall be in violation of this Code and shall, upon conviction before any court of competent jurisdiction, be penalized within the limits and as provided by the laws of the State of Louisiana.
SECTION 156 - PENALTY TO ENGINEER: FINES
A person engaged in the practice, calling, or profession as an operating engineer, or engaged in the operation of any boiler, steam engine, internal combustion engine, refrigeration and/or air conditioning equipment and hoisting or portable equipment as defined in this Code, under the terms of this Code, without being at the time the holder of a proper and valid license issued by the Mechanical Inspection Division provided herein, shall be in violation of this Code and shall, upon conviction before any court of competent jurisdiction, be penalized within the limits and as provided by the laws of the State of Louisiana.
SECTION 157 - ALTERATION, REPRODUCTION, TRANSFER OR RENTING OF LICENSE
It is a violation of this Code for a license holder to alter, reproduce, transfer, lend or rent his license to another individual for their use. It is a violation of this Code for any license holder to use any license that is not a part of his own record.
SECTION 158 - SIMULTANEOUS CHARGE OF MORE THAN ONE PLANT
It is unlawful for a licensed operating engineer, from the Mechanical Inspection Division, to be concurrently or simultaneously in charge of more than one plant or location at the same time.
(M.C.S., Ord. No. 22939, § 9, 12-20-07; M.C.S., Ord. No. 25920, § 1, 6-19-14; M.C.S., Ord. No. 27443, § 1, 6-15-17; M.C.S., Ord. No. 30235, § 1, 2-27-25)