§ 1110 — REFRIGERATION PIPING SYSTEM TEST

The Philadelphia Code (2026 Code: The Philadelphia Code and Home Rule Charter current through October 8, 2026) · Philadelphia Code Subcode M, § 1110

Corpus is an independent public-information project, not the official City of Philadelphia website. Stable reference: corpuslaw.us/code/298af8a6-6df4-4ff2-bf75-f0ba40ad52d1

SECTION 1110 REFRIGERATION PIPING SYSTEM TEST

* * * [Delete Section 1110.3 and replace as follows:] M-1110.3 Test gases. The medium used for pressure testing the refrigerant system shall be one of the following inert gases: oxygen-free nitrogen, helium, argon or premixed nonflammable oxygen-free nitrogen with a tracer of gas of hydrogen or helium. For R-744 refrigerant systems, carbon dioxide shall be allowed as the test medium, For R-718 refrigerant systems, water shall be allowed as the test medium. M-1110.3.1 Test gases not permitted. Oxygen, air, refrigerants other than those identified in Section 1110.3, combustible gases and mixtures containing such gases shall not be used as the pressure test medium. * * * [Delete Section 1110.5 and replace as follows:] M-1110.5 Piping system strength test. Refrigerating system components and refrigerant piping shall be tested in accordance with ASME B31.5 or this section. Separate tests for isolated portions of the system are permitted and provided that all required portions are tested at least once. Pressurize with test gas for a minimum of 10 minutes to not less than the lower of (a) the lowest design pressure for any system component, or (b) the lowest value of set pressure for any pressure relief devices in the system. The design pressures for determination of test pressure shall be the pressure identified on the label nameplate of the condensing unit, compressor, compressor unit, pressure vessel, or other system component with a nameplate. A passing test result shall have no rupture or structural failure of any system component or refrigerant piping. Refrigerant popping and tubing greater than 3/4 inches in diameter shall be tested in accordance with ASHRAE 15. [Delete Section 1110.6 in its entirety, without substitution] [Delete Section 1110.7 in its entirety, without substitution] * * *

Ask a question about Philadelphia law

Corpus searches the Philadelphia sections it holds and shows the ones that match, with their citations. Free, no sign-in.