Sec. 92.116. - Automatic and manual fire alarm systems; power supply, signals.

All automatic fire alarm systems and manual fire alarm systems required to be installed under the provisions of Sections 92.110 to 92.122, inclusive, shall: 1) Be equipped with both primary and secondary power supplies. a) The primary power supply shall be from the building 110 volt AC service. b) The secondary (standby) power supply of a type specified by NFPA #72, as referenced by the Ohio Building Code. 2) Be equipped with both audible and visible signals, located as described below: a) In places of public assembly: i) Both audible and visible signals shall be installed throughout; ii) A minimum of one visible signal shall be installed in the direct viewing path of the occupants (that is, adjacent to the stage or screen in theaters); and iii) The private operating mode may be used in places of public assembly with an occupant load greater than 1,000, when approved by the Fire Official. b) In residential occupancies: i) A minimum of one audible signal shall be installed in each dwelling unit, sleeping room and/or guest room; ii) A minimum of one visible signal shall be installed in the dwelling unit, sleeping room or guest room of all hearing impaired occupants, but not less than one unit in each 75, or fraction thereof, shall be so supplied; and iii) Audible and visible signals shall be installed in the public and common areas conforming with Section 92.116(C). c) In all other occupancies audible and visible signals shall be installed conforming with Section 92.116(C). 3) Audible and visible signals, required by Section 92.116(B), shall be installed as follows, except as modified herein: a) Audible signals shall be installed to operate as follows: i) Signals operating in the public mode shall produce an alarm signal through the protected area of not less than 15 dBA above the average ambient noise level. ii) Signals operating in the private mode shall produce an alarm signal in a constantly attended location, staffed by persons responsible for directing or initiating emergency procedures, of not less than ten dBA above the average ambient noise level. b) Visible signals shall be installed as follows: i) Not less than 80 inches nor more than 108 inches above the finished floor. ii) Not less than six inches below the ceiling. iii) Not to exceed 100 feet between devices.

(Ord. 32042-23, passed 6-7-23)

Ask a question about Dayton law

Corpus searches the Dayton sections it holds and shows the ones that match, with their citations. Free, no sign-in.