§ 42-137 — Testing of backflow preventions devices

Code of Ordinances, City of Olive Branch, Mississippi (Supp. No. 14: codified through Ordinance of June 17, 2025) · Olive Branch Code of Ordinances § 42-137

Corpus is an independent public-information project, not the official City of Olive Branch website. Stable reference: corpuslaw.us/code/2b001c14-8795-4f81-8799-81d8670b0f88

Sec. 42-137. - Testing of backflow preventions devices.

(a) Tests Required. Each reduced pressure principal backflow prevention assembly, double check valve assembly, and pressure vacuum breaker shall be tested immediately after installation, after repairs of any kind, and annually. Any backflow preventer found to be non-functional shall be repaired and re-tested within 14 days of the initial test. (b) Certified Testers. Only backflow preventer testers certified by the Mississippi State Department of Health shall test backflow preventers located in the water system. (c) Notification. The water system shall notify the owner of each backflow preventer 60 days prior to the date that the backflow preventer is scheduled to be tested.

(Ord. of 4-16-24(1), § VI)