Sec. 49-1131. - Grease traps.
Grease traps shall be installed as follows:
(a) The maximum rated flow capacity through each trap shall be 50 gpm.
(b) The minimum rated flow capacity shall be 20 gpm.
(c) Water jacketed grease traps are not approved.
(d) Four separate fixtures shall be the maximum connected to or discharged into any one grease trap.
(e) Flow control devices shall not have adjustable or removable parts. Each fixture connected to a grease trap shall have a flow control or restricting device installed in the drain outlet and shall be readily accessible.
(f) The total capacity in gallons of fixtures discharging into a grease trap shall not exceed 2½ times the gpm flow rate of the grease interceptors.
(g) A grease trap may be used as a fixture trap for a single fixture only when the horizontal distance to the fixture is less than four feet and the vertical distance to the fixture outlet is less than 2½ feet.
(h) No food waste disposal unit shall be connected to or discharged into a grease trap.
(j) Inside grease traps shall be cleaned as often as necessary but not less frequent than at least every 30 days. Cleaning shall consist of removing interceptor contents until empty and cleaning sides and bottom.