Rate-of-flow indicator.
Omaha Municipal Code § 54-116
in effectSec. 54-116. - Rate-of-flow indicator.
There shall be provided a rate-of-flow indicator on the pump discharge line leading to the filters which shall be calibrated for measuring both water for filtration and backwash. The activating element creating the pressure differential for indication of flow shall be installed with adequate clear distance upstream and downstream to obtain a reasonable degree of accuracy. The rate of flow indicators shall be installed in accordance with manufacturer's specifications. The rate-of-flow indicator shall be calibrated for and provided with a scale reading in gallons per minute and shall have a range of ten percent below the established filtration rate and ten percent above the backwash rate.
(Code 1980, § 54-116)
Source: City of Omaha, Municipal Code and City Charter (Municode Library, library.municode.com)URL: https://library.municode.com/ne/omaha/codes/code_of_ordinances?nodeId=OMMUCOCHGEORVOII_CH54SWPO_ARTIIPUCOSWPO_DIV3DECORE_S54-116RA-FINFetched: 10/28/2026