Sec. 49-1309. - Relief vents.

Soil and waste stacks in buildings exceeding ten branch intervals shall be provided with a relief vent at each tenth interval installed as follows: (a) Begin with the top floor. (b) The size of the relief vent shall be equal to the size of the vent stack to which it is connected. (c) The lower end of each relief vent shall connect to the soil or waste stack through a wye below the horizontal branch serving the floor. (d) The upper end shall connect to the vent stack through a wye not less than 42 inches above the floor level. (See Figure 49-1309.)

(Ord. No. 40524, § 1, 10-20-15)