Sec. 49-1728. - Size of building sewer.

The following requirements shall apply to sewer size: (a) Dwelling units and townhouses require at least a four-inch inside diameter building sewer. (b) Commercial buildings or multiple dwelling units require at least a six-inch inside diameter building sewer, but not less than the building drain size. (c) For land parcels used for multiple dwelling units, commercial and industrial buildings, the private sewer shall be one size larger than the required size for the combined buildings' total fixture units (see section 49-901) but at least eight inches in diameter. See article XIV for cleanout and manhole requirements.

(Ord. No. 40524, § 1, 10-20-15)